Smartcool, Precision air conditioning, W 2 w2 – Airedale SmartCool 11-233kW User Manual

Page 98: Electrical data – w2w2

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

98

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Electrical Data – W2W2

SC19D055-W2W2

SC19D070-W2W2

SC19D080-W2W2

Standard Dry Cooler Match

2 x DR40

2 x DR55

2 x DR55

Unit Data –Full Function W2W2

(1)

Nominal Run Amps

A

65.7

77.2

84.7

Maximum Start Amps

A

127.2

152.8

171.5

Recommended Mains Fuse Size

A

80

100

100

Max Mains Incoming Cable Size

mm²

70

70

70

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – W2W2

Nominal Run Amps

A

49.6

61

68.5

Maximum Start Amps

A

111

136.6

155.3

Recommended Mains Fuse Size

A

63

80

80

Evaporator Fan Motor – Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Compressor – Compressor 1 , Circuit 1 & 2

(3)

Motor Size

kW

4.58

5.55

6.31

Nominal Run Amps

A

8.5

11.39

13.27

Locked Rotor Amps

A

70

87

100

Type of Start

Direct On Line

Compressor – Compressor 2, Circuit 1 & 2

(3)

Motor Size

kW

4.58

5.55

6.31

Nominal Run Amps

A

8.5

11.39

13.27

Locked Rotor Amps

A

70

87

100

Type of Start

Direct On Line

Standard Dry Cooler Match – AC Motor Per Fan

Quantity x Motor Size

kW

2 x 0.6

3 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS

Electric Heating

Stage of Reheat

2

2

2

Number of Elements

6

6

6

Rating (Total)

kW

21

21

21

Current Per Phase

A

30.31

30.31

30.31

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

Standard Size Fan Motor – EC Motor – Per Fan

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

2 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Larger Size Motor – EC Motor – Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Condenser Match – EC Motor-Per Fan

Quantity x Motor Size

kW

2 x 0.73

3 x 0.73

3 x 0.73

Full Load Amps

A

3.3

3.3

3.3

SCAF Condenser Match – Motor- Per Fan

Quantity x Motor Size

kW

2 x 1.4

3 x 1.4

3 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for full function units with standard selections for heating, humidification, supply air fans and
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor

W