Precision air conditioning, Smartcool, Air cooled models – Airedale SmartCool 11-233kW User Manual

Page 65: T ec hn ic al, X2x2), Performance data – air cooled models, Cooling duties standard condenser match

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

65

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Air Cooled Models

(X2X2)

Performance Data – Air Cooled Models

Cooling Duties

Standard Condenser Match

X2X2

Ambient Temperature (°C)

Model

Air On °C DB

25

30

35

40

46

%RH

TC

(KW)

SC

(KW)

TC

(KW)

SC

(KW)

TC

(KW)

SC

(KW)

TC

(KW)

SC

(KW)

TC

(KW)

SC

(KW)

SC19D055-X2X2-0
2 x CR50

22/50

52.4

48.8

52.4

48.8

51.7

48.5

49.1

47.4

45.7

45.7

24/45

53.5

52.4

53.5

52.4

52.8

52.0

50.2

50.2

46.7

46.7

26/40

54.5

54.5

54.5

54.5

53.7

53.7

51.1

51.1

47.6

47.6

SC19D070-X2X2-0
2 x CR65

22/50

65.2

59.8

65.2

59.8

64.9

59.6

62.2

58.4

58.7

56.9

24/45

66.9

64.2

66.9

64.2

66.5

64.1

63.7

63.0

60.1

60.1

26/40

68.3

68.3

68.3

68.3

67.9

67.9

65.0

65.0

61.4

61.4

SC19D080-X2X2-0
2 x CR65

22/50

74.2

67.2

74.2

67.2

73.1

66.7

69.8

65.3

65.7

63.5

24/45

76.1

72.2

76.1

72.2

74.9

71.6

71.5

70.2

67.3

67.3

26/40

77.7

77.6

77.7

77.5

76.3

76.3

72.9

72.9

68.7

68.7

SC25D080-X2X2-0
2 x CR65

22/50

75.7

69.8

75.7

69.8

74.4

69.2

71.1

67.5

66.9

65.4

24/45

77.6

75.1

77.6

75.1

76.2

74.4

72.8

72.7

68.5

68.5

26/40

79.3

79.3

79.3

79.3

77.7

77.7

74.3

74.3

70.0

70.0

SC25D090-X2X2-0
2 x CR65

22/50

82.4

76.5

82.4

76.5

80.4

75.6

76.8

73.8

72.1

71.6

24/45

84.6

82.3

84.6

82.3

82.3

81.2

78.6

78.6

73.9

73.9

26/40

86.4

86.4

86.4

86.4

84.0

84.0

80.2

80.2

75.5

75.5

SC25D100-X2X2-0
2 x CR80

22/50

93.9

85.6

93.9

85.6

92.1

84.6

88.0

82.6

82.8

80.0

24/45

96.3

91.7

96.3

91.7

94.3

90.7

90.1

88.7

84.8

84.8

26/40

98.3

98.3

98.3

98.3

96.1

96.1

91.9

91.9

86.5

86.5

SC31D100-X2X2-0
2 x CR80

22/50

95.8

86.2

95.8

86.2

93.6

85.2

89.3

83.1

83.7

80.4

24/45

98.3

92.5

98.3

92.5

95.9

91.4

91.5

89.4

85.8

85.8

26/40

100.3

99.3

100.3

99.3

97.8

97.8

93.3

93.3

87.7

87.7

SC31D120-X2X2-0
2 x CR105

22/50

109.6

99.1

109.6

99.1

109.0

98.8

104.1

96.5

97.9

93.6

24/45

112.4

106.4

112.4

106.4

111.6

106.0

106.7

103.9

100.4

100.4

26/40

114.8

114.4

114.8

114.4

113.9

113.9

108.9

108.9

102.5

102.5

SC31D130-X2X2-0
2 x CR105

22/50

117.2

105.7

117.2

105.7

115.9

105.1

110.9

102.8

104.5

99.9

24/45

120.2

113.4

120.2

113.4

118.7

112.7

113.6

110.5

107.0

107.0

26/40

122.8

122.1

122.8

122.1

121.2

121.2

116.0

116.0

109.3

109.3

TC=Total Cooling SC=Sensible Cooling
(1) All data quoted is gross
(2) Deduct fan gain for nett duties, refer to Mechanical Data

T

ec
hn
ic

al

Advertising