Water Cooled Models (W2W2)

Performance Data – Water Cooled Models


Cooling Duties

Cooling Capacity (1)

Condenser Entering / Leaving Temperature - Based on ∆T of 5°C

Air On °C DB

25°C/30°C

30°C/35°C

35°C / 40°C

40°C/45°C

/%RH

TC

(kW)

SC

(kW)

THR
(kW)

TC

(kW)

SC

(kW)

THR
(kW)

TC

(kW)

SC

(kW)

THR
(kW)

TC

(kW)

SC

(kW)

THR
(kW)

SC19D055-W2W2-0
2 x DR40

22/50

52.4

48.8

67.2

52.4

48.8

67.2

51.9

48.6

67.1

49.2

47.4

66.4

24/45

53.5

52.4

68.3

53.5

52.4

68.3

53.0

52.2

68.2

50.2

50.2

67.4

26/40

54.5

54.5

69.3

54.5

54.5

69.3

54.0

54.0

69.2

51.2

51.2

68.4

SC19D070-W2W2-0
2 x DR55

22/50

65.2

59.8

83.9

65.2

59.8

83.9

65.2

59.8

83.9

63.1

58.8

83.3

24/45

66.9

64.2

85.6

66.9

64.2

85.6

66.9

64.2

85.6

64.7

63.4

84.9

26/40

68.3

68.3

87.0

68.3

68.3

87.0

68.3

68.3

87.0

66.1

66.1

86.3

SC19D080-W2W2-0
2 x DR55

22/50

74.2

67.2

95.8

74.2

67.2

95.8

74.2

67.2

95.8

71.5

66.0

94.9

24/45

76.1

72.2

97.7

76.1

72.2

97.7

76.1

72.2

97.7

73.3

71.0

96.7

26/40

77.7

77.5

99.3

77.7

77.5

99.3

77.7

77.5

99.3

74.8

74.8

98.3

SC25D080-W2W2-0
2 x DR55

22/50

75.7

69.8

97.3

75.7

69.8

97.3

75.7

69.8

97.3

72.9

68.4

96.3

24/45

77.6

75.1

99.2

77.6

75.1

99.2

77.6

75.1

99.2

74.7

73.6

98.1

26/40

79.3

79.3

100.8

79.3

79.3

100.8

79.3

79.3

100.8

76.3

76.3

99.7

SC25D090-W2W2-0
2 x DR70

22/50

82.4

76.5

106.9

82.4

76.5

106.9

82.4

76.5

106.9

79.7

75.2

106.0

24/45

84.6

82.3

109.1

84.6

82.3

109.1

84.6

82.3

109.1

81.7

80.9

108.1

26/40

86.4

86.4

110.9

86.4

86.4

110.9

86.4

86.4

110.9

83.5

83.5

109.9

SC25D100-W2W2-0
2 x DR70

22/50

93.9

85.6

122.1

93.9

85.6

122.1

93.9

85.6

122.1

90.6

83.8

121.3

24/45

96.3

91.7

124.5

96.3

91.7

124.5

96.3

91.7

124.5

92.9

90.0

123.6

26/40

98.3

98.3

126.6

98.3

98.3

126.6

98.3

98.3

126.6

94.8

94.8

125.6

SC31D100-W2W2-0
2 x DR70

22/50

95.8

86.2

124.1

95.8

86.2

124.1

95.8

86.2

124.1

92.1

84.4

122.8

24/45

98.3

92.5

126.6

98.3

92.5

126.6

98.3

92.5

126.6

94.5

90.7

125.3

26/40

100.3

99.3

128.7

100.3

99.3

128.7

100.3

99.3

128.7

96.5

96.5

127.3

SC31D120-W2W2-0
2 x DR95

22/50

109.6

99.1

141.7

109.6

99.1

141.7

109.6

99.1

141.7

105.0

96.9

140.2

24/45

112.4

106.4

144.6

112.4

106.4

144.6

112.4

106.4

144.6

107.7

104.3

143.0

26/40

114.8

114.4

147.0

114.8

114.4

147.0

114.8

114.4

147.0

109.9

109.9

145.3

SC31D130-W2W2-0
2 x DR95

22/50

117.2

105.7

151.6

117.2

105.7

151.6

117.2

105.7

151.6

112.2

103.4

150.2

24/45

120.2

113.4

154.7

120.2

113.4

154.7

120.2

113.4

154.7

115.0

111.1

153.1

26/40

122.8

122.1

157.4

122.8

122.1

157.4

122.8

122.1

157.4

117.5

117.5

155.7

TC=Total Cooling SC=Sensible Cooling THR=Total Heat of Rejection

(1) All data quoted is gross

(2) Deduct fan gain for net duties, refer to Mechanical Data

(3) Interpolate for water temperatures between those quoted, do not extrapolate

(4) Water flow rate (l/s)= THR/(4.19 x ∆T) at 100% Water

W