Smartcool, Precision air conditioning, C 0 c0 – Airedale SmartCool 11-233kW User Manual

Page 156: Electrical data - c0c0

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

156

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data - C0C0

SC19D033-C0C0-0

SC19D038-C0C0-0

SC19D045-C0C0-0

Unit Data Full Function C0C0

(1)

Nominal Run Amps

A

69.3

69.3

69.3

Maximum Start Amps

A

69.3

69.3

69.3

Recommended Mains Fuse Size

A

80

80

80

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only C0C0

Nominal Run Amps

A

7.6

7.6

7.6

Maximum Start Amps

A

7.6

7.6

7.6

Recommended Mains Fuse Size

A

10

10

10

Evaporator Fan - Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

OPTIONAL EXTRAS

Electric Heating

Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.47

45.47

45.47

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade EC Motor - Per Fan

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

2 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Second upgrade EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

(1) Values given for function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

SC25D045-C0C0-0

SC25D50-C0C0-0

SC25D55-C0C0-0

Unit Data Full Function – C0C0

(1)

Nominal Run Amps

A

77.7

77.7

77.7

Maximum Start Amps

A

115.2

115.2

115.2

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only C0C0

Nominal Run Amps

A

16.00

16.00

16.00

Maximum Start Amps

A

53.5

53.5

53.5

Recommended Mains Fuse Size

A

25

25

25

Evaporator Fan - Motor - Per Fan

Motor Type

AC

AC

AC

Quantity x Motor Size

(2)

kW

3 x 2.38

3 x 2.38

3 x 2.38

Full Load Amps

A

5

5

5

Locked Rotor Amps

A

17.5

17.5

17.5

OPTIONAL EXTRAS

Electric Heating

Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.

45.5

45.5

Humidifier

Capacity

Kg/hr

15

15

15

Rating

A

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade Fan Motor - EC Motor - Per Fan

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

3 x 2.2

3 x 2.2

3 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Second upgrade Motor - EC Motor - Per Fan

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

(1) Values given for function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

C

0

C0

Advertising