Precision air conditioning, Smartcool, W 2 c0 – Airedale SmartCool 11-233kW User Manual

Page 117: Electrical data- w2c0 continued

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

117

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data- W2C0 Continued

SC31D055-W2C0-0

SC31D065-W2C0-0

SC31D075-W2C0-0

Standard Dry Cooler Match

1 x DR70

1 x DR95

1 x DR95

Unit Data Full Function- W2C0

Nominal Run Amps

(1)

A

84.2

84.4

84.4

Maximum Start Amps

A

177.9

197.5

211.1

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

70

70

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only - W2C0

Nominal Run Amps

A

56.2

56.4

58.7

Maximum Start Amps

A

169.3

169.4

202.4

Recommended Mains Fuse Size

A

63

63

80

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Compressor 1 , Circuit 1

Motor Size

(3)

kW

7.2

9.5

9.5

Nominal Run Amps

A

12.9

16.9

16.9

Locked Rotor Amps

A

92

130

130

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

kW

9.5

9.5

10.86

Nominal Run Amps

A

16.9

16.9

19.2

Locked Rotor Amps

A

130

130

163

Type of Start

Direct On Line

Standard Dry Cooler Match - Motor Per Fan

AC

EC

EC

Quantity x Motor Size

(2)

kW

4 x 0.6

4 x 0.88

4 x 0.88

Full Load Amps

A

2.62

1.65

1.65

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.5

45.5

45.5

Humidifier

Capacity

kg/hr

8

8

8

Rating

kW

6

6

6

Full Load Amps

A

8.7

8.7

8.7

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Dry Cooler Match - EC Motor-Per Fan

Quantity x Motor Size

(2)

kW

4 x 0.73

4 x 1.68

4 x 1.68

Full Load Amps

A

3.3

2.6

2.6

Dry Cooler Match - SCAF Fan

Quantity x Motor Size

(2)

kW

4 x 1.4

4 x 1.94

4 x 1.94

Full Load Amps

A

6

3.4

3.4

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor