Smartcool, Precision air conditioning, Ou t d oor – Airedale SmartCool 11-233kW User Manual

Page 202: Performance data – condensers, Standard condenser fan

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

202

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Performance Data – Condensers

Standard Condenser Fan

Mean Condensing

Ambient

Temperature °C

25°C

30°C

35°C

40°C

45°C

48°C

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

CR12

35

8.8

3.3

-

-

-

-

40

13.8

8.8

3.4

-

-

-

45

19.0

14.0

8.9

3.6

-

-

50

24.4

19.2

14.1

9.1

3.8

-

55

29.8

24.7

19.5

14.4

9.3

4.1

CR16

35

11.9

5.0

-

-

-

-

40

18.2

12.0

5.2

-

-

-

45

24.7

18.4

12.1

5.4

-

-

50

31.3

25.0

18.6

12.3

5.6

-

55

38.2

31.8

25.4

19.0

12.6

6.5

CR22

35

15.4

6.2

-

-

-

-

40

24

15.5

6.4

-

-

-

45

32.8

24.2

15.7

6.7

-

-

50

41.7

33.1

24.6

16.0

7.0

-

55

51.0

42.3

33.7

25.1

16.4

7.7

CR26

35

19.2

7.8

-

-

-

-

40

29.9

19.4

8.0

-

-

-

45

40.9

30.3

19.6

8.4

-

-

50

52.1

41.4

30.7

20.0

8.8

-

55

63.5

52.9

42.1

31.4

20.5

9.9

CR30

35

19.8

8.1

-

-

-

-

40

30.6

20.0

8.4

-

-

-

45

41.7

30.9

20.2

8.7

-

-

50

53.1

42.1

31.3

20.5

9.2

-

55

64.8

53.8

42.8

31.9

21.0

9.8

CR35

35

25.4

10.5

-

-

-

-

40

39.4

25.7

10.9

-

-

-

45

53.6

39.7

26.0

11.3

-

-

50

68.1

54.2

40.3

26.4

11.8

-

55

83.1

69.0

55.0

41.1

27

12.9

CR50

35

33.7

13.7

-

-

-

-

40

52.6

34.0

14.2

-

-

-

45

71.7

53.1

34.4

14.8

-

-

50

91.3

72.5

53.8

35.1

15.5

-

55

111.5

92.6

73.7

54.8

35.9

16.9

CR60

35

42.3

65.9

-

-

-

-

40

65.9

42.7

17.9

-

-

-

45

89.8

66.6

43.2

18.6

-

-

50

114..3

91.0

67.6

44.0

19.5

-

55

139.5

116.0

92.5

68.9

45.1

20.3


(1)

Output kW refers to the condenser heat rejection.

O

U

T

D

OOR

Advertising