Smartcool, Precision air conditioning, Technical data – Airedale SmartCool 11-233kW User Manual

Page 64: System operating limits, Tec hn ic al

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

64

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Technical Data

IMPORTANT

The following information is for general guidance; refer to the certified drawings
provided for installation.

CAUTION

ALL work MUST be carried out by technically trained competent personnel.

The equipment contains live electrical and moving parts, ISOLATE prior to
maintenance or repair work. The electrical panel in the SmartCool may remain live
with the control panel door open.

Ensure Electrical lock-off procedures are conducted.

General

Once the refrigeration pipework is complete the electrical supply can be connected by
routing the cables through the appropriate casing hole and connecting the cables as per
the wiring diagram supplied with each unit

A fused and isolated electrical supply of the appropriate rating should be installed.

As standard the equipment is designed for 400V, 3 Phase, Neutral and earth 50Hz to all
relevant IEE regulations, British standards and IEC requirements.

All mains and interconnecting wiring should be carried out to National and Local codes.

Wires should be capable of carrying the maximum load current under non-fault conditions
at the stipulated voltage.

Avoid large voltage drops on cable runs, particularly low voltage wiring

CAUTION

Each unit requires an independently fused and isolated power supply.

System Operating Limits

X2 Models




For conditions outside those quoted, please contact Airedale.

Cooling

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55%

Outdoor Temperature - Standard Condenser Match

-20°C to +41°C

Outdoor Temperature - Larger Condenser Match

-20°C to +48°C

W2 Models

Cooling

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55%

Condenser Minimum Entering Temperature °C

+25°C

Condenser Maximum Leaving Water Temperature °C

+45°C

For conditions outside those quoted, please contact Airedale.

C0 Models





Cooling

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55%

Water Entering Temperature

+5°C to +10°C

Water Leaving Temperature

+10°C to +16°C

Conditions quoted at 100% Water.

For conditions outside those quoted, please contact Airedale.

T

ec
hn
ic

al

Advertising