Precision air conditioning, Smartcool, W 2 f0 – Airedale SmartCool 11-233kW User Manual

Page 127: Mechanical data – w2f0 continued

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

127

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Mechanical Data – W2F0 Continued

SC19D064-W2F0

SC19D070-W2F0

SC19D076-W2F0

Standard Dry Cooler Match

1 x DR95

1 x DR95

1 x DR95 (

EC)

Capacity

Nom Cooling (Gross) – W2

(1)

kW

63.2

68.7

75.3

Nom Cooling (Gross) - F0 (Free Cooling)

(2)

kW

74.4

74.4

74.4

Total Heat of Rejection –W2

kW

81.6

89.2

99.1

Capacity Steps

2

2

2

Fan Gain

(5)

kW

1.7

1.7

1.7

Dimensions - W x D x H

mm

1985 x 890 x 1980

1985 x 890 x 1980

1985 x 890 x 1980

Weight - Machine / Operating

kg

950 / 980

950 / 980

960 / 990

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)

Material/Colour

Frame: Anodised Aluminium Frame with Black Nylon Corners

Evaporator

Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling/Dehum Stages

2/1

2/1

2/1

Condenser

(3)

Stainless steel Brazed Plate

Water Volume

l

Glycol Flow

l/s

4

4.4

4.9

Pressure Drop Condenser

kPa

59.6

70.8

86.7

Glycol Coil

Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Water Volume

l

29.4

32.4

32.4

Glycol Flow

l/s

2.93

2.93

2.93

Pressure Drop F0

kPa

125.8

147.8

178.6

Unit

Water flow

l/s

4

4.4

4.85

Pressure drop

kPa

185.42

218.66

265.34

Dry Cooler

Water Volume

l

55.9

55.9

55.9

Flowrate

l/s

4

4.4

4.9

Pressure Drop

kPa

76.8

89.7

106.8

Fan Motor

Backwards Curved, Centrifugal direct drive

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Speed @25Pa ESP/ maximum ESP

rpm

1340 /1360

1340 /1360

1340 /1360

Maximum ESP

Pa

49

49

49

Nominal Airflow

m³/s

5.1

5.1

5.1

Compressor - Scroll

Configuration

Dual Cool - Circuit 1 Tandem Compressors (Water Cooled)

Circuit 2 Free Cooling

Quantity - W2

2

2

2

Oil Charge Volume - W2

l

2 x 3.3

2 x 3.3

2 x 3.3

Oil Type

Polyolester

Connections

Water Inlet / Outlet – W2

mm

42

42

42

Glycol Connections Inlet/Outlet – F0

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

3

3

3

OPTIONAL EXTRAS

Hot Gas Reheat - X

Nom Heating (Gross)

kW

9.7

9.7

9.7

Electric Heating (Total)

kW

31.5

31.5

31.5

Humidifier

Capacity

kg/hr

15

15

15

Feed/Drain

3/4" BSPF Braided flexible hose / 19mm hose connection

Condensate Pump

Head

m

10.8

10.8

10.8

Flow

l/m

5

5

5

Drain

10mm Stainless Steel Stub Connection

First upgrade Fan Motor - EC Motor

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

2 x 3.1

Speed @ 25Pa

rpm

1364 / 1520

1364 / 1520

1364 / 1520

Maximum ESP

Pa

216

216

216

Fan Gain

(5)

kW

1.73

1.73

1.73

Second upgrade Fan Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

(5)

kW

N/A

N/A

N/A

Low Pressure Hot Water

(4)

Copper Tube/Aluminium Fin

Capacity Gross

kW

26

26

26

Water Flow (Nominal)

l/s

0.58

0.58

0.58

Pressure Drop

kPA

10.1

10.1

10.1

LPHW Connection Sizes

mm

22

22

22

(1) Entering air 24°C/ 45% RH condenser water in / out 35 / 40°C
(2) Entering air 24°C/ 45% RH condenser water in / out 7/12°C and based on water.
(3) Pressure drop through condenser, free cooling coil, 3 port valve, Head pressure control valve and unit pipe work
(4) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C
(5) Fan gain based on 25Pa ESP @ nominal air volume. Fan gain will change as airflow and ESP change.

W

2

F0

Advertising