26

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Installation Data

Oil Charging Guide

The compressor(s) is supplied with oil for up to approximately 20m of interconnecting
pipework.

Compressors

The compressor oil sight glass (where fitted) should indicate a level of between 1/3
and 2/3 to ensure correct operation.

Run the compressor(s) for a minimum of 1 hour to check oil return and motor function. For
tandem or trio sets, checks should be performed in part load operation.

1. Use a temperature metering device on each circuit:

2. Check operation and superheat readings are within acceptable limits.

3. Check suction and discharge pressure are within acceptable limits.

4. Check there is NO foaming in the compressor sight glass. This would indicate the

presence of liquid returning to the compressor.


5. Check sight glass following commissioning and top oil up if level has fallen below

minimum.

6. If oil has been added to allow for long pipe runs, large number of oil traps, etc,

and the level in the compressors keep decreasing; the oil return in the system is
insufficient. A pipework design check is required.

IMPORTANT

It is possible to check the oil level of a compressor a few moments after it is turned off.
However the oil level must not be observed when the compressor is turned off. The
refrigerant in the system can give a false indication of this level.

In this case the oil level should be at about 1/3.

IMPORTANT

For applications with pipework in excess of 20m, long vertical runs, special
operating conditions etc, ensure good oil return is guaranteed AND add sufficient
oil to the system.

REMEMBER, TOO MUCH or TOO LITTLE OIL can cause compressor damage. As a
rule NO MORE than 10% additional oil should be added to any system.

ALWAYS use the oil specified by the compressor manufacturer.

Polyolester oil is extremely hygroscopic and will rapidly absorb moisture from the
air. The oil must therefore not be left open to the atmosphere for long periods of
time. The system must be correctly evacuated to ensure all moisture is removed.


Pressure switch settings

High pressure switch cut-out

40.3 bar

(583psi)

High pressure switch cut-in

30.0 bar

(435psi)

High pressure switch differential

10.3 bar

(148psi)

Low pressure switch cut-out

1.0 bar

(14psi)

Low pressure cut-in

3.0 bar

(43psi)

Low pressure differential

2.0 bar

(29psi)

In

s

ta

ll

a

tion