Precision air conditioning, Smartcool, C 0 c0 – Airedale SmartCool 11-233kW User Manual

Page 157: Electrical data - c0c0 continued

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

157

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Electrical Data - C0C0 Continued

SC31D55-C0C0-0

SC31D65-C0C0-0

SC31D75-C0C0-0

Unit Data Full function – C0C0

(1)

Nominal Run Amps

A

77.1

77.1

77.1

Maximum Start Amps

A

77.1

77.1

77.1

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – C0C0

Nominal Run Amps

A

15.4

15.4

15.4

Maximum Start Amps

A

15.4

15.4

15.4

Recommended Mains Fuse Size

A

25

25

25

Evaporator Fan - Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

OPTIONAL EXTRAS

Electric Heating

Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.5

45.5

45.5

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

(1) Values given for function units with standard selections for heating, humidification, supply air fans.
(2) Stated motor power is based on maximum electrical power absorbed

C

0

C0

Advertising