Installation, Maintenance and Commissioning Manual :6877419 02/2013

Input / Outputs

The inputs and outputs of the controller are listed below

SmartCool

Analogue Inputs

Analogue Outputs

AI 1 (B1-GND)

Universal Return Air Humidity

AO1(Y1-G0)

0 - 10Vdc

Supply Air Fans

AI 2 (B2- +VDC)

Universal

Constant air volume or
constant pressure

AO2 (Y2-G0)

0 - 10Vdc

CCT1 CR/DR Fans
or CCT1 CW
Regulating Valve

AI 3 (B3- +VDC)

Universal

CCT 1 Liquid Transducer or
CW Supply temp sensor

AO3 (Y3-G0)

0 - 10Vdc

CCT2 CR/DR Fans
or CCT2 CW
Regulating Valve

AI 4 (B4-BC4)

Passive

Return Air Temperature

AO4 (Y4-G0)

0 - 10Vdc

Thyristor
Heating/LPHW
Regulating Valve

AI 5 (B5-BC5)

Passive

Supply Air Temperature

AO5 (Y5-G0)

0 - 10Vdc

CCT1 WX HP
Regulating Valve

AI 6 (B6- +VDC)

Universal

CCT 1 Discharge
Temperature

AO6 (Y6-G0)

0 - 10Vdc

CCT2 WX HP
Regulating Valve

AI 7 (B7-GND)

Universal

CCT 2 Liquid Transducer or
Dual Cool Water Temperature

AI 8 (B8-GND)

Universal

CCT 2 Discharge
Temperature or Dual Cool
Frost Protection

AI 9 (B9-BC9)

Passive

CCT 1 Supply Water
Temperature

AI 10 (B10-BC10)

Passive

CCT 2 Supply Water
Temperature or Glycol Dry
Cooler Ambient Temperature

Digital Inputs

Digital Outputs

DI 1 (ID1-IDC1)

24Vac

Remote On-Off

DO 1 (NO1-C1)

NO Relay

Heat 1

DI 2 (ID2-IDC1)

24Vac

Airflow Switch

DO 2 (NO2-C1)

NO Relay

Heat 2

DI 3 (ID3-IDC1)

24Vac

Filter Change Switch

DO 3 (NO3-C1)

NO Relay

Heat 3

DI 4 (ID4-IDC1)

24Vac

Phase Rotation

DO 4 (NO4-C4)

NO Relay

CCT1 Compressor 1
or CPY Hum Enable

DI 5 (ID5-IDC1)

24Vac

Water Flood
Detection/Condensate Pump

DO 5 (NO5-C4)

NO Relay

CCT1 Compressor 2

DI 6 (ID6-IDC1)

24Vac

Fire/Smoke Detection

DO 6 (NO6-C4)

NO Relay

CCT1 Liquid Line
Solenoid

DI 7 (ID7-IDC1)

24Vac

Refrigerant Leak Detection

DO 7 (NO7-C7)

NO Relay

(SSR)

Non-Critical Alarm

DI 8 (ID8-IDC1)

24Vac

Over Heat Cut Out (Auto)

DO 8 (NO8-C8)

NO / NC

Relay

Critical Alarm

DI 9 (ID9-IDC9)

24Vac

CCT1 Compressor 1 Status

DO 9 (NO9-C9)

NO Relay

CCT2 Compressor 1

DI 10 (ID10-IDC9)

24Vac

CCT1 Compressor 2 Status

DO 10 (NO10-C9)

NO Relay

CCT2 Compressor 2

DI 11 (ID11-IDC9)

24Vac

CCT1 Low Pressure Trip

DO 11 (NO11-C9)

NO Relay

CCT2 Liquid Line
Solenoid

DI 12 (ID12-IDC9)

24Vac

CCT2 Low Pressure Trip

DO 12 (NO12-C12)

NO / NC

Relay (SSR)

Hot Gas Soloniod
Valve

DI 13 (ID13-IDC13)

24Vac

CCT2 Compressor 1 Status

DO 13 (NO13-C13)

NO / NC

Relay

CPY Hum Enable

DI 14 (ID14-IDC13)

24Vac

CCT2 Compressor 2 Status

DO 14 (NO14-C14)

NO / NC

Relay (SSR)

Not Used

DI 15 (ID15-IDC15)

24Vac

Not Used

DO 15 (NO15-C15)

NO / NC

Relay (SSR)

Not Used

DI 16 (ID16-IDC15)

24Vac

Not Used

DO 16 (NO16-C16)

NO Relay

CCT1 Dry Cooler
Enable

DI 17 (ID17-IDC17)

24Vac

CCT1 Dry Cooler fault

DO 17 (NO17-C16)

NO Relay

CCT2 Dry Cooler
Enable

DI 18 (ID18-IDC17)

24Vac

CCT2 Dry Cooler fault

DO 18 (NO18-C16)

NO Relay

Not Used