Precision air conditioning, Smartcool, Troub les hoo ting – Airedale SmartCool 11-233kW User Manual

Page 183

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

183

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Code

Description

A

u

to

Reset

U

n

it

D

isa

b

led

C

o

m

p

o

n

en

t

D

isa

b

le

d

Cause

Action

AL003

Humidity Probe Alarm

Ÿ

Ÿ

Indicates that there is a fault with

the corresponding probe, possible
causes are the sensor going open

circuit or there is a wiring fault. All

sensor alarms are auto reset once

the fault has been rectified.

Humidity control will be disabled until the

sensor fault is rectified.

AL004

Differential Pressure
Sensor Alarm

Ÿ

Ÿ

Constant Air Volume will be disabled and

fan speed will revert to fixed speed set

point

AL004

Floor Void Differential
Pressure Sensor Alarm

Ÿ

Ÿ

Constant Pressure Control will be disabled

and fan will revert back to fixed fan speed

set point

AL005

Liquid Pressure Circuit
1 Probe Alarm

Ÿ

Ÿ

Head Pressure Control is disabled on

circuit 1 and the condenser fans is

increased to 100%

AL005

Inlet Chilled Water
Temperature Probe
Alarm

Ÿ

Ÿ

Alarm will be generated

AL006

Return Air Temperature
Sensor Alarm

Ÿ

Ÿ

Cooling and Heating control is disabled

until the sensor is fixed

AL007

Supply Air
Temperature Probe
Alarm

Ÿ

Ÿ

Supply air control is disabled and unit

controls to return air control

AL008

Circuit 1 Discharge
Temp Probe Alarm

Ÿ

Ÿ

Alarm will be generated

AL009

Liquid Pressure Circuit
2 Probe Alarm

Ÿ

Ÿ

Head Pressure Control is disabled on

circuit 2 and the condenser fans are

increased to 100%

AL009

Supply Water
Temperature Alarm

Ÿ

Ÿ

Alarm is generated

AL010

Coil Temperature
Probe Alarm

Ÿ

Ÿ

Alarm is generated

AL010

Circuit 2 Discharge
Temp Probe Alarm

Ÿ

Ÿ

Alarm is generated

AL011

Circuit 1 Supply Water
Temp Probe Alarm

Ÿ

Ÿ

Free cooling is disabled

AL012

Circuit 2 Supply Water
Temp Probe Alarm

Ÿ

Ÿ

Alarm is generated

AL012

Ambient Temperature
Probe Alarm

Ÿ

Ÿ

Free cooling is disabled

AL013

Air Flow Fail

û

Ÿ

Ÿ

Indicates the air flow switch has not
detected any airflow for 60 seconds
once the main fan is switched on.

The alarm will auto reset 3 times and lock

out to a manual reset

AL014

Circuit 1 Compressor 1
Status

Ÿ

Ÿ

This alarm indicates the status of

compressor.

The alarm is generated if the

controller output is active but the

feed back from the contactor has

not changed.

The alarm will de-activate the

corresponding compressor.

AL015

Circuit 1 Compressor 2
Status

Ÿ

Ÿ

AL016

Circuit 1 Inverter
Compressor Status

Ÿ

Ÿ

AL017

Circuit 2 Compressor 1
Status

Ÿ

Ÿ

AL018

Circuit 2 Compressor 2
Status

Ÿ

Ÿ

AL019

Circuit 2 Inverter
Compressor Status

Ÿ

Ÿ

AL020

Filter Change Alarm

Indicates that the filters on the unit

possibly need changing.

Alarm will need to be manually reset once

the filter has been changed.