Precision air conditioning, Smartcool, X2 c0 – Airedale SmartCool 11-233kW User Manual

Page 85: Electrical data – x2c0 continued

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

85

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data – X2C0 Continued

SC19D064-X2C0-0

SC19D070-X2C0-0

SC19D076-X2C0-0

Standard Condenser Match

1 x CR105

1 x CR105

1 x CR105

Unit Data – Full Function - X2C0

Nominal Run Amps

A

80.2

81.6

85.4

Maximum Start Amps

A

223.9

218.9

257.9

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – X2C0

Nominal Run Amps

A

54.4

57.3

65

Maximum Start Amps

A

198.2

194.6

237.5

Recommended Mains Fuse Size

A

63

80

80

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Compressor 1 , Circuit 1

Motor Size

kW

10.9

12.2

13.7

Nominal Run Amps

A

19.2

20.7

24.5

Locked Rotor Amps

A

163

158

197

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

kW

10.9

12.2

13.7

Nominal Run Amps

A

19.2

20.7

24.5

Locked Rotor Amps

A

163

158

197

Type of Start

Direct On Line

Standard Condenser Match - AC Motor Per Fan

Quantity x Motor Size

kW

3 x 0.6

3 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.47

45.47

45.47

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Condenser Match - EC Motor-Per Fan

Quantity x Motor Size

kW

3 x 0.73

3x 0.73

3 x 0.73

Full Load Amps

A

3.3

3.3

3.3

Condenser Match - SCAF Fan

Quantity x Motor Size

kW

3 x 1.4

3 x 1.4

3 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor

X2
C0