Smartcool, Precision air conditioning, Design data – water cooled & free cooling – Airedale SmartCool 11-233kW User Manual

Page 22

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

22

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Design Data – Water Cooled & Free Cooling

Dry Cooler (kW)

The dry cooler design duty is equivalent to the Total Heat of Rejection (THR) from the indoor unit.

This value can be taken from the performance data in the technical manual using the following.

Parameters required are:
·

Ambient conditions (°C dB) Airedale recommend a 10°C lower than the EWT.

·

Glycol content (%)

·

Entering & leaving water/glycol temperatures (°C) (EWT and LWT)

·

Mean condensing temperature (°C) Based on 5°C above leaving water/glycol temperature

Calculation of Design
Volumetric Flow Rate (l/s)

The maximum design volumetric flow rate can be calculated using the following equation:

V&

=

Q

r x Cp x ΔT

Where:
Q

=

Total Heat Rejection (kW).

DT

=

Temperature Difference between Water/Glycol Entering/ Leaving (°C).

r

=

Density. Refer to table below.

Cp

=

Specific heat capacity. Refer to table below.

Calculation of Indoor Unit
Pressure Drop (

DPs)

The maximum indoor unit pressure drop can be calculated using the following equation:

DPs= DPw x Pc

Using the volumetric flow rate calculated above, the pressure drop (

DPw) can be taken from the

relevant pressure drop graph..

Where:

DPs

=

Maximum Water/Glycol Pressure Drop for the indoor unit (kPa).

DPw

=

Equivalent Water Pressure Drop for indoor unit (kPa).

P

c

=

% Glycol Pressure Drop Correction Factor @ 20°C Water Temperature.

Refer to table below.

The resultant pressure drop (

DPs) is the maximum pressure drop based on the indoor unit

running at the prescribed conditions.

This will typically occur when the water/glycol temperature is approximately 20°C and the
water/glycol is being circulated through the free cooling coil and through the water cooled
condenser.

The indoor unit pressure drop will reduce at other operating conditions.

Specific Heat Capacity (Cp)

Water/Glycol Temperature °C

Ethylene Glycol (Volume) / Freezing Point °C

0% / 0°C

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

F

c

F

c

F

c

F

c

F

c

20

4.183

3.972

3.815

3.645

3.468

25

4.181

3.981

3.826

3.660

3.485

30

4.179

3.989

3.838

3.674

3.502

35

4.178

3.998

3.849

3.688

3.518

40

4.179

4.007

3.861

3.702

3.535

45

4.181

4.015

3.872

3.716

3.552

Density (

r)

Water/Glycol Temperature °C

Ethylene Glycol (Volume) / Freezing Point °C

0% / 0°C

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

F

c

F

c

F

c

F

c

F

c

20

998

1013

1030

1045

1060

25

997

1012

1028

1043

1058

30

996

1010

1026

1041

1055

35

994

1008

1024

1039

1053

40

992

1006

1022

1036

1050

45

990

1003

1020

1035

1048

Pressure Drop Correction
Factor (P

c)

Water/Glycol Temperature °C

Ethylene Glycol (Volume)

0%

10%

20%

30%

40%

P

c

P

c

P

c

P

c

P

c

20

0.983

1.0125

1.054

1.0958

1.15


In

s

ta

ll

a

tion

Advertising