Precision air conditioning, Smartcool, W 2 c0 – Airedale SmartCool 11-233kW User Manual

Page 107: Mechanical data – w2c0

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

107

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Mechanical Data – W2C0

SC19D033-W2C0

SC19D038-W2C0

SC19D045-W2C0

Standard Dry Cooler Match

1 x DR40

1 x DR55

1 x DR55

Capacity

Nom Cooling (Gross) – W2

(1)

kW

29.1

36.8

42.3

Nom Cooling (Gross) – C0

(2)

kW

61.6

67.9

74.4

Total Heat of Rejection – W2

kW

36.7

46.0

53.1

Capacity Steps

2

2

2

Fan Gain

(6)

kW

0.66

1.0

1.7

Dimensions – W x D x H

Mm

1985 x 890 x 1980

1985 x 890 x 1980

1985 x 890 x 1980

Weight – Machine / Operating

(3)

Kg

850 / 880

860 / 890

860 / 890

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint – Black Grey (RAL 7021)

Material/Colour

Frame: Anodised Aluminium Frame with Black Nylon Corners

Evaporator

Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling/Dehum Stages

2/1

2/1

2/1

Cooling Coil – C0

Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling /Dehum Stages

1 (Modulated) / 1

Water Volume

l

29.4

32.4

32.4

Water Flow

l/s

2.44

2.72

3.14

Pressure Drop C0

kPa

30.9

27.8

35.0

Condenser

Stainless steel Brazed Plate

Water Volume

l

Glycol Flow

l/s

1.78

2.25

2.6

Pressure Drop Condenser

kPa

86.13

50.48

66.22

Dry Cooler

Water Volume

L

23.1

43.2

43.2

Flowrate

l/s

1.78

2.25

2.6

Pressure Drop

kPa

40.8

27

31.9

Fan Motor

Backwards Curved, Centrifugal direct drive

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Speed @25Pa / Maximum ESP

RPM

964 / 1360

1117 / 1360

1340 / 1360

Maximum ESP

Pa

438

302

49

Nominal Airflow

m³/s

3.7

4.3

5.1

Compressor – Scroll

Configuration – W2C0

Dual Cool – Circuit 1 Tandem Compressors (Water Cooled) / Circuit 2 Chilled Water

Quantity – W2C0

2

2

2

Oil Charge Volume – W2C0

l

2 x 1.57

2 x 1.57

2 x 1.57

Oil Type

Polyolester

Connections

Water Inlet / Outlet –W2

mm

35

35

35

Water Inlet / Outlet – C0

mm

35

35

35

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

3

3

3

OPTIONAL EXTRAS

Hot Gas Reheat -

Nom Heating (Gross)

kW

8.1

8.9

9.5

Electric Heating (Total)

kW

21

21

21

Humidifier

Capacity

kg/hr

8

8

8

Feed/Drain

3/4" BSPF Braided flexible hose / 19mm hose connection

Condensate Pump

Head

m

10.8

10.8

10.8

Flow

l/m

5

5

5

Drain

10mm Stainless steel Stub Connection

First upgrade Motor - EC Motor

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

2 x 3.1

Speed @ 25Pa / Maximum ESP

rpm

986 / 1510

1145 / 1520

1364 / 1510

Maximum ESP

Pa

589

453

216

Fan Gain

(6)

kW

0.65

1.03

1.73

Second upgrade Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

(6)

kW

N/A

N/A

N/A

Low Pressure Hot Water

(5)

Copper Tube/Aluminium Fin

Capacity Gross

kW

22.16

24.45

26

Water Flow (Nominal)

l/s

0.49

0.54

0.58

Pressure drop

kPa

9.4

9.7

10.1

LPHW Connection Sizes

mm

22

22

22

(1) Entering air 24°C/45% RH condensing water in / out: 35/40°C
(2) Entering air 24°C/45% RH water 7°C/12°C
(3) Machine weight Includes a refrigerant charge / Operating weight includes calculated water volume
(4) Based on air temperature of 15.5 °C

leaving the evaporator coil

(5) Based upon low pressure hot water 82 °C inlet / 71°C outlet. Air on 20°C.
(6) Fan gain based on 25 Pa ESP @ nominal air volume. Fan gain figure will change as airflow and ESP change.

W

2

C0

Advertising