Precision air conditioning, Smartcool, Troub les hoo ting – Airedale SmartCool 11-233kW User Manual

Page 185

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

185

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Code

Description

A

u

to

Reset

U

n

it

D

isa

b

led

C

o

m

p

o

n

en

t

D

isa

b

le

d

Cause

Action

AL038

Low Return Air
Temperature

Ÿ

Ÿ

Ÿ

AL039

High Supply Air
Temperature

Ÿ

Ÿ

Ÿ

AL040

Low Supply Air
Temperature

Ÿ

Ÿ

Ÿ

AL041

Circuit 1 High
Pressure

Ÿ

Indicates that circuit 1 has

been exposed to high pressure.

Circuit 1 will be shut down,

Once the pressure within circuit 1 has

decreased to a safe level the alarm can be

manually reset

AL042

Circuit 2 High
Pressure

Ÿ

Indicates that circuit 2 has

been exposed to high pressure.

Circuit 2 will be shut down.

Once the pressure within circuit 2 has

decreased to a safe level the alarm can be

manually reset

AL043

EEV Driver 1
Motor Error

Ÿ

Indicates an motor error within

EEV driver 1. During this alarm

circuit 1 is switched off.

This alarm can be manually reset once the

problem with the EEV is resolved


Troub

les
hoo

ting

Advertising