Smartcool, Precision air conditioning, C 0 c0 – Airedale SmartCool 11-233kW User Manual

Page 160: Interconnecting wiring – c0c0, Cable installation, Indoor controls only, Remote on/off, Run/standby network

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

160

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Interconnecting Wiring – C0C0

INDOOR

UNIT

L1

¡

ç

Mains Incoming Supply 400V / 3PH + N / 50Hz

L2

¡

ç

L3

¡

ç

N

¡

ç

PE

¡

ç

Indoor Controls Only

INDOOR

UNIT

560

¡

è

Volt Free Alarm N/O

Non-Critical Alarm

561

¡

ç

Volt Free Alarm Common

563

¡

è

Volt Free Alarm N/O

Critical Alarm

564

¡

ç

Volt Free Alarm Common

565

¡

è

Volt Free Alarm N/C

502

¡

è

Fire Shutdown input

583

¡

ç

Healthy in N/C Condition

Remote On/Off

INDOOR

UNIT

502

¡

è

Remote On/OFF

522

¡

ç

Run/Standby Network

INDOOR

UNIT

Rx-/Tx-

¡

çè

Use Awg20/22 twisted pair (with overall shield)

cable, Belden ref. 8762 (Airedale ref:

6110316), or equivalent, for

network

çè

¡

Rx-/Tx-

INDOOR

UNIT
N + 1

Rx+/Tx+

¡

зи

зи

¡

Rx+/Tx+

GND

¡

зи

зи

¡

GND

CABLE INSTALLATION

In line with IEE Wiring Regulations, the following should be observed:
·

Extra low voltage control cables (ELV) and mains power cable should be segregated by a
minimum distance of 50mm

·

If cables must cross, it is recommended that they cross at right angles

·

Airedale recommends that ELV cables are screened at one end to earthed enclosures