Installation, Maintenance and Commissioning Manual :6877419 02/2013

Humidifier Bottle
Information

Limit Values for the supply water with Medium to High conductivity in an immersed
electrode humidifier.

Min

Max

Hydrogen ions

pH

7

8.5

Specific conductivity at 20°C

σR, 20°C

μS/cm

300

1250

Total dissolved solids

TDS

mg/l

(1)

(1)

Dry residue at 180°C

R180

mg/l

(1)

(1)

Total hardness TH

mg/l CaCO3

100(2)

400

Temporary hardness

mg/l CaCO3

60(3)

300

Iron + Manganese

mg/l Fe + Mn

0

0.2

Chlorides

ppm- Cl

0

30

Silica

mg/l SiO2

0

20

Residual chlorine

mg/l Cl

0

0.2

Calcium sulphate

mg/l CaSO4

0

100

Metallic impurities

mg/l

0

0

Solvents, diluents, soaps, lubricants

mg/l

0

0

(1) Values depending on specific conductivity; in general: TDS ≅ 0.93 * σ20; R180 ≅ 0.65 * σ20
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-

Limit Values for the supply water with Medium to Low conductivity in an immersed
electrode humidifier

Min

Max

Hydrogen ions

pH

7

8.5

Specific conductivity at 20°C

σR, 20°C

μS/cm

125

500

Total dissolved solids

TDS

mg/l

(1)

(1)

Dry residue at 180°C

R180

mg/l

(1)

(1)

Total hardness TH

mg/l CaCO3

50(2)

250

Temporary hardness

mg/l CaCO3

30(3)

150

Iron + Manganese

mg/l Fe + Mn

0

0.2

Chlorides

ppm- Cl

0

20

Silica

mg/l SiO2

0

20

Residual chlorine

mg/l Cl

0

0.2

Calcium sulphate

mg/l CaSO4

0

60

Metallic impurities

mg/l

0

0

Solvents, diluents, soaps, lubricants

mg/l

0

0


(1) Values depending on specific conductivity; in general: TDS ≅ 0.93 * σ20; R180 ≅ 0.65 * σ20
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-


Warning: no relation can be demonstrated between water hardness and
conductivity.
IMPORTANT WARNING: do not treat water with softeners!
This could cause corrosion of the electrodes or the formation of foam, leading to
potential operating problems or failures.

IMPORTANT

The water supply should conform to Local Water Regulations and within the
following guidelines:

Supply water pressure between 1.0 barg to 8.0 barg, > 8.0 bar a pressure reducing valve
should be fitted.
A minimum flow rate of 1.21 l/min is required.

The humidifier inlet is fitted with a braided flexible hose, having 3/4” BSPF connection.

IMPORTANT

Ensure the union between the humidifier assembly and supply hose is fully
tightened. Any looseness, misalignment or damage to the union can lead to
water leakage.

CAUTION

It is recommended that a shut off valve and a mechanical strainer be fitted to the
water supply prior to the humidifier assembly.

Water Conductivity

As standard the humidifier is fitted with the standard conductivity cylinder which covers
the majority of water supplies. Low and high conductivity options can be specified at
order.