Electrical Data – X2C0 Continued

SC25D045-X2C0-0

SC25D050-X2C0-0

SC25D055-X2C0-0

Standard Condenser Match

1 x CR65

1 x CR65

1 x CR80

Unit Data - X2C0

Nominal Run Amps

A

64.8

64.4

82.2

Maximum Start Amps

A

151.6

143.6

175.9

Recommended Mains Fuse Size

A

80

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only X2C0

Nominal Run Amps

A

47.8

47.5

54.2

Maximum Start Amps

A

134.5

126.6

167.2

Recommended Mains Fuse Size

A

63

63

63

Evaporator Fan Motor - Per Fan

Motor Type

AC

AC

AC

Quantity x Motor Size

kW

3 x 2.38

3 x 2.38

3 x 2.38

Full Load Amps

A

5

5

5

Locked Rotor Amps

A

17.5

17.5

17.5

Compressor 1 , Circuit 1

Motor Size

kW

6.31

7.19

7.19

Nominal Run Amps

A

13.27

12.87

12.87

Locked Rotor Amps

A

100

92

92

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

kW

6.31

7.19

9.46

Nominal Run Amps

A

13.27

12.87

16.93

Locked Rotor Amps

A

100

92

130

Type of Start

Direct On Line

Standard Condenser Match - AC Motor Per Fan

Quantity x Motor Size

kW

2 x 0.6

2 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

2

2

3

Number of Elements

6

6

9

Rating (Total)

kW

21

21

31.5

Current Per Phase

A

30.31

30.31

45.47

Humidifier

Capacity

kg/hr

8

8

8

Rating

kW

6

6

6

Full Load Amps

A

8.67

8.67

8.67

First upgrade Fan Motor - EC Motor - Per
Fan

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

3 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Standard Condenser Match - EC Motor-Per Fan

Quantity x Motor Size

kW

2 x 0.73

2 x 0.73

3 x 0.73

Full Load Amps

A

3.3

3.3

3.3

Condenser Match - SCAF Fan

Quantity x Motor Size

kW

2 x 1.4

2 x 1.4

3 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor