Smartcool, Precision air conditioning, X2 c0 – Airedale SmartCool 11-233kW User Manual

Page 84: Electrical data –x2c0

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

84

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Electrical Data –X2C0

SC19D033-X2C0-0

SC19D038-X2C0-0

SC19D045-X2C0-0

Standard Condenser Match

1 x CR50

1 x CR65

1 x CR65

Unit Data Full function - X2C0

Nominal Run Amps

A

51.7

54.5

56.4

Maximum Start Amps

A

113.2

130.2

143.2

Recommended Mains Fuse Size

A

63

63

63

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling only –X2C0

Nominal Run Amps

A

29.8

35.6

39.4

Maximum Start Amps

A

91.3

111.2

126.1

Recommended Mains Fuse Size

A

40

40

50

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Compressor 1 , Circuit 1

Motor Size

kW

4.6

5.6

6.3

Nominal Run Amps

A

8.5

11.4

13.3

Locked Rotor Amps

A

70

87

100

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

kW

4.6

5.6

6.3

Nominal Run Amps

A

8.5

11.39

13.27

Locked Rotor Amps

A

70

87

100

Type of Start

Direct On Line

Standard Condenser Match - AC Motor Per Fan

Quantity x Motor Size

kW

2x 0.6

2 x 0.6

2 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

2

2

2

Number of Elements

6

6

6

Rating (Total)

kW

21

21

21

Current Per Phase

A

30.31

30.31

30.31

Humidifier

Capacity

kg/hr

8

8

8

Rating

kW

6

6

6

Full Load Amps

A

8.67

8.67

8.67

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

2 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Condenser Match - EC Motor-Per Fan

Quantity x Motor Size

kW

2 x 0.73

2 x 0.73

2 x 0.73

Full Load Amps

A

3.3

3.3

3.3

Condenser Match - SCAF Fan

Quantity x Motor Size

kW

2 x 1.4

2 x 1.4

2 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor


X2

C0

Advertising