Precision air conditioning, Smartcool, X2x2 – Airedale SmartCool 11-233kW User Manual

Page 71: Electrical data – x2x2 continued

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

71

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Electrical Data – X2X2 Continued

SC25D080-X2X2

SC25D090-X2X2

SC25D100-X2X2

Standard Condenser Match -

2 x CR65

2 x CR65

2 x CR80

Unit Data Full Function - X2X2

(1)

Nominal Run Amps

A

90.5

89.9

100.7

Maximum Start Amps

A

177.3

169.1

213.7

Recommended Mains Fuse Size

A

125

125

125

Max Mains Incoming Cable Size

mm²

70

70

70

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – X2X2

Nominal Run Amps

A

74.3

73.7

84.5

Maximum Start Amps

A

161.1

152.9

197.5

Recommended Mains Fuse Size

A

100

100

100

Evaporator Fan - Motor - Per Fan

Motor Type

AC

AC

AC

Quantity x Motor Size

(2)

kW

3 x 2.38

3 x 2.38

3 x 2.38

Full Load Amps

A

5

5

5

Locked Rotor Amps

A

17.5

17.5

17.5

Compressor 1 , Circuit 1 & 2

(3)

Motor Size

kW

6.31

7.19

7.19

Nominal Run Amps

A

13.27

12.87

12.87

Locked Rotor Amps

A

100

92

92

Type of Start

Direct On Line

Compressor 2, Circuit 1 & 2

(3)

Motor Size

kW

6.31

7.19

9.46

Nominal Run Amps

A

13.27

12.87

16.93

Locked Rotor Amps

A

100

92

130

Type of Start

Direct On Line

Standard Condenser Match - AC Motor Per Fan

Quantity x Motor Size

kW

2 x 0.6

2 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

Electric Heating

Stage of Reheat

2

2

3

Number of Elements

6

6

9

Rating (Total)

kW

21

21

31.5

Current Per Phase

A

30.31

30.31

45.47

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

Standard Size Fan Motor - EC Motor –Per Fan

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Larger Size Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

2 x 3.1

2 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Standard Condenser Match - EC Motor-Per Fan

Quantity x Motor Size

kW

2 x 0.73

2 x 0.73

3 x 0.73

Full Load Amps

A

3.3

3.3

3.3

SCAF Condenser Match - Motor-Per Fan

Quantity x Motor Size

kW

2 x 1.4

2 x 1.4

3 x 1.4

Full Load Amps

A

6

6

6

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor

X2X2