Precision air conditioning, Smartcool, Troub les hoo ting – Airedale SmartCool 11-233kW User Manual

Page 187

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

187

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Code

Description

A

u

to

Reset

U

n

it

D

is

ab

led

C

o

m

p

o

n

en

t

D

isa

b

le

d

Cause

Action

AL055

EEV Driver 2 MOP Alarm

Ÿ

Indicates that the

evaporating temperature

has exceeded the MOP

limit. During alarm the EEV
modulates the valve closed

to reduce the operating

pressure whilst maintaining

superheat.

This alarm can be manually reset once

the system has brought the

evaporating temperature below the

MOP limit.

AL056



EEV Driver 2 LOP Alarm

Ÿ

Indicates that the

evaporating temperature

has exceeded the LOP

limit. During alarm the EEV

modulates the valve open

to increase the operating

pressure whilst maintaining

superheat.

This alarm can be manually reset once

the system has brought the

evaporating temperature below the

LOP limit.

AL057

EEV Driver 2 Low Superheat
Alarm

Ÿ

Indicates the superheat

has exceeded the low

superheat limit. During the

alarm compressor 2 is

switched off.

This alarm can be manually reset once

the system has brought the superheat

above the low super heat limit.

AL058

EEV Driver 2 EEV Not Closed
After Power Fail

Ÿ

Indicates that the EEV did
not close once power was

restored, during alarm

compressor 2 is switched

off.

This alarm is manually reset.

AL059

EEV Driver 2 High Superheat
Alarm

Ÿ

Indicates the superheat

has exceeded the high

superheat limit. During the

alarm compressor 2 is

switched off.

This alarm can be manually reset once

the system has brought the superheat

below the high super heat limit.

AL060

EEV Driver 2 S1 Probe Error
Evap. Pressure

Ÿ

Indicates an error with the

evaporating pressure

sensor. During alarm the

controller will automatically

switch off the compressor.

This alarm can be manually reset once

the sensor is proven to be working

correctly.

AL061

EEV Driver 2 S2 Probe Error
Suction Line Temp

Ÿ

Indicates an error with the

suction line temperature

sensor. During alarm the

controller will automatically

switch off the compressor.

This alarm can be manually reset once

the sensor is proven to be working

correctly.

AL062

EEV Driver 2 S3 Probe Suction
Line Temp

Ÿ

Indicates an error with the

suction line temperature

sensor. During alarm the

controller will automatically

switch off the compressor.

This alarm can be manually reset once

the sensor is proven to be working

correctly.

AL063

EEV Driver 3 Motor Error

Ÿ

Indicates an motor error

within EEV diver 2. During
this alarm compressor 2 is

switched off.

This alarm can be manually reset once

the problem with the EEV is resolved

AL064

EEV Driver 3 EEPROMM Error

Ÿ

Indicates that there has

been an error between the

data stored within the

eeprom memory and the

data stored in the

controller. During the alarm

the EEV is closed and

compressor 2 is switched

off.


This alarm can be manually reset once

the problem with the EEV is resolved

Troub

les
hoo

ting