Smartcool, Precision air conditioning, X2 c0 – Airedale SmartCool 11-233kW User Manual

Page 82: Mechanical data – x2c0 continued

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

82

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Mechanical Data – X2C0 Continued

SC31D055-X2C0-0

SC31D065-X2C0-0

SC31D075-X2C0-0

Standard Condenser Match -

1 x CR80

1 x CR105

1 x CR105

Capacity

Nom Cooling (Gross) – X2

(1)

kW

52.7

61.0

65.7

Nom Cooling (Gross) – C0

(2)

kW

107

121.6

135.2

Capacity Steps

3

2

3

Fan Gain

(7)

kW

1.25

2.06

3.22

Dimensions - W x D x H

mm

3113 x 890 x 1980

3113 x 890 x 1980

3113 x 890 x 1980

Weight - Machine / Operating

(3)

kg

1150 / 1200

1150 / 1210

1160 / 1210

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)

Material/Colour

Frame: Anodised Aluminium Frame with Black Nylon Corners

Evaporator – X2

Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling/Dehum Stages

3/1

2/1

3/1

Cooling Coil – C0

Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling /Dehum Stages

1(Modulated)/ 1

Water Volume

l

44

44

44

Water Flow

l/s

4.18

4.7

5.16

Pressure Drop

kPa

46.7

55.9

65.2

Fan Motor

Backwards Curved, Centrifugal direct drive

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Speed @ 25Pa / Maximum ESP

1061 / 1520

1261 / 1520

1480 / 1520

Maximum ESP

Pa

528

330

77

Nominal Airflow

m³/s

5.8

6.9

7.9

Compressor - Scroll

Configuration

Dual Cool - Circuit 1 Tandem Compressors (Refrigeration) / Circuit 2 Chilled water

Quantity

2

2

2

Oil Charge Volume

l

2 x 3.3

2 x 3.3

2 x 3.3

Oil Type

Polyolester

Refrigeration

Single Circuit

Refrigeration Control & Type

Thermostatic Expansion Valve (Optional EEV)

Refrigeration Type

R410A

Holding Charge

Inert Gas

Charge (Total)

kg

15.9

24.2

24.2

Connections

Liquid (Sweat) – X2

in

7/8

7/8

7/8

Discharge (Sweat) – X2

in

1 1/8

1 1/8

1 1/8

Water Inlet / Outlet – C0

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4-600

Quantity

4

4

4

OPTIONAL EXTRAS

Hot Gas Reheat - X

(5)

Nom Heating (Gross)

kW

14.6

16.1

16.1

Electric Heating (Total)

kW

31.5

31.5

31.5

Humidifier

Capacity

kg/hr

8

8

8

Feed/Drain

3/4" BSPF Braided flexible hose / 19mm hose connection

Condensate Pump

Head

m

10.8

10.8

10.8

Flow

l/m

5

5

5

Drain

10mm Stainless Steel Stub Connection

First upgrade Fan Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

(7)

kW

N/A

N/A

N/A

Second upgrade Fan Motor - EC Motor

Quantity x Motor Size

kW

N/A

N/A

N/A

Speed @ 25Pa / Maximum ESP

rpm

N/A

N/A

N/A

Maximum ESP

Pa

N/A

N/A

N/A

Fan Gain

(7)

kW

N/A

N/A

N/A

Low Pressure Hot Water

(6)

Copper Tube/Aluminium Fin

Capacity Gross

kW

40.6

43.8

45.2

Water Flow (Nominal)

l/s

0.9

0.97

1.01

Pressure drop

kPa

35.9

35.9

35.9

LPHW Connection Sizes

mm

22

22

22

(1) Entering air 24°C/45% RH 35°C Ambient
(2) Entering air 24°C/45% RH water 7/12°C
(3) Machine weight includes a refrigerant charge / operating weight includes calculated water volume
(4) For refrigerant charges, refer to Unit Refrigerant Charge (kg/Circuit)
(5) Based on air temperature of 15.5°C

leaving the evaporator coil

(6) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C
(7) Fan gain based on 25Pa ESP @ nominal air volume. Fan gain figure will change as airflow and ESP change.

X2

C0

Advertising