Precision air conditioning, Smartcool, Troubleshooting – Airedale SmartCool 11-233kW User Manual

Page 215: Ou t d oo r

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

215

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Troubleshooting

Airedale Matched Outdoor Units

FAULT

POSSIBLE CAUSE

REMEDY/ACTION

Unit will not start

No power

Check power supply to the controller

Wired incorrectly

Check wire connections in accordance with wiring
diagram on control box lid

Loose wires

Check all wires, connections, terminals etc

Head pressure too high

Condenser coil clogged or dirty

Clean condenser

Overcharge of refrigerant, normally troublesome
in warm weather

Reclaim excess refrigerant from system

Air or other non-condensable gas in system

Evacuate system and re-charge with new
refrigerant

Head pressure controller faulty

Refer to Indoor unit

Fan not operating or operating inefficiently

Refer to Indoor unit

Head pressure too low

Fan operating too fast in low ambient conditions Refer to Indoor unit

Condenser fan not operating -
power on

Power supply failure

Check power supply at circuit breaker

Wiring to motor

Check voltage at motor terminals

Motor / fan assembly jammed

Isolate unit and check free rotation of motor/fan
assembly, if faulty - replace

Motor internal overheat protector tripped

Carry out continuity check at terminals “TK” in
motor terminal box, if tripped and motor hot -
check bearings, if tripped and motor cold - replace
motor

Faulty motor windings/capacitor

Motor humming would indicate fault in motor or
capacitor, check windings for continuity and if OK
replace capacitor

Minimum speed set too low

Refer to Indoor unit

Faulty pressure sensor

Check electrical connections are secure at
controller and pressure sensor, replace controller
and sensor (as they are matched sets)

Faulty fan speed controller

Refer to Indoor unit

Condenser fan runs too fast

High ambient condition or excessive re-
circulation of air around condenser coil

Check installation against design

Minimum set speed setting incorrect

Adjust as necessary

Incorrect pressure sensor setting

Adjust sensor screw as necessary

Faulty fan speed controller

Refer to Indoor unit

Faulty pressure sensor

Refer to Indoor unit

Condenser fans runs only
slowly

Incorrect pressure setting

Adjust sensor screw as necessary

Faulty fan speed controller

Refer to Indoor unit

Faulty pressure sensor

Refer to Indoor unit

Motor/capacitor faulty

Replace

O

U

T

D

OO

R

Advertising