Code

Description

A

u

to

Reset

U

n

it

D

isa

b

led

C

o

m

p

o

n

en

t

D

isa

b

le

d

Cause

Action

AL065

EEV Driver 3 MOP Alarm

Ÿ

Indicates that the

evaporating temperature

has exceeded the MOP

limit. During alarm the EEV
modulates the valve closed

to reduce the operating

pressure whilst maintaining

superheat.

This alarm is manually reset once the

system has brought the evaporating

temperature below the MOP limit.

AL066

EEV Driver 3 LOP Alarm

Ÿ

Indicates that the

evaporating temperature

has exceeded the LOP

limit. During alarm the EEV

modulates the valve open

to increase the operating

pressure whilst maintaining

superheat.

This alarm is manually reset once the

system has brought the evaporating

temperature below the LOP limit.

AL067

EEV Driver 3 Low Superheat
Alarm

Ÿ

Indicates the superheat

has exceeded the low

superheat limit. During the

alarm compressor 2 is

switched off.

This alarm is manually reset once the

system has brought the superheat

above the low super heat limit.

AL068

EEV Driver 3 EEV Not Closed
After Power Fail

Ÿ

Indicates that the EEV did
not close once power was

restored, during alarm

compressor 2 is switched

off.

This alarm is manually reset.

AL069

EVD1 pLAN Communications
Offline

Ÿ

Ÿ

Indicates an error with the

pLAN connection which the

controller communicates

with EVD1. This alarm will

shut circuit 1 down.

This alarm is automatically reset once

the pLAN fault is rectified.

AL070

EVD2 pLAN Communications
Offline

Ÿ

Ÿ

Indicates an error with the

pLAN connection which the

controller communicates

with EVD2. This alarm will

shut circuit 1 down.

This alarm is automatically reset once

the pLAN fault is rectified.

AL071

EVD3 pLAN Communications
Offline

Ÿ

Ÿ

Indicates an error with the

pLAN connection which the

controller communicates

with EVD3. This alarm will

shut circuit 2 down.

This alarm is automatically reset once

the pLAN fault is rectified.

AL072

EVD4 pLAN Communications
Offline

Ÿ

Ÿ

Indicates an error with the

pLAN connection which the

controller communicates

with EVD4. This alarm will

shut circuit 2 down.




This alarm is automatically reset once

the pLAN fault is rectified.

AL073

Clock Alarm

Ÿ

Ÿ

Indicates an error with the

real time clock on-board

the controller. During alarm

any time zones set up

would be ignored.

Once the clock returns to functioning

correctly the alarm will be

automatically reset and any time ones

setup will be restored.

AL074

Frost Protection Alarm

Ÿ

Ÿ

Indicates that the controller

has disabled any dx

cooling to prevent

damaging the coils from

frost.

This alarm is automatically reset once

any danger of damage is removed.

AL075

High Supply Water Temperature

Ÿ

Ÿ

Indicates that the supply

water temperature is above

the maximum value of

supply water temperature

permitted.

Alarm is automatically reset once the

value of supply water temperature is
lower than the maximum value. This

enables a circuit change over on dual

cool units