VF Transmitter Menu Tree Software Release 04.02.XX
Level 1
Level 2
Level 3
Range
Description
Output Config (cont.)
GVF Spike
Filter
State
Enable, Disable
Enable spike filtering
No GVF Len
1-60
Number of good
measurements during
initialization before GVF
spike filter passes
measurements as
‘good’
Length
0
– 60 readings
Defines the number of
consecutive valid
measurements before
displaying flow rate
GVF Spike
Filter Adv
Up Count
1-60
Number of counts to
INCREMENT the GVF
Bad Quality counter
when measured VF
quality is below the
minimum
Down Count
1-60
Number of counts to
DECREMENT the GVF
Bad Quality counter
when measured GVF
quality is below the
minimum
Percent
0
– 100 %
Defines percent
difference of the
previous measurement
over the range below
which the flow rate is
deemed valid
Percent Len
2-60
Number of good
measurements before
GVF spike filter passes
measurements as
‘good’