System faults – CiDRA SONARtrac PW VF-100 User Manual

Page 261

Advertising
background image

20838-01 Rev 09

Page J-2

System Faults:

Item
No

PROBLEM

POSSIBLE
CAUSE

DIAGNOSTIC
METHOD

DIAGNOSTIC
RESULT

COMMENTS

1

System does
not come on
or was
working and
stopped
working

No power to
system

Check input power with
volt meter

Yes - there is power and
power is within system
specs of 100 - 240 volts
(AC units) or 18

– 36

volts (DC units)

See Below

No - power to system or
power is below spec

Check external wiring / circuit breakers, etc. to
ensure power and that power is within spec
Connect to alternate power source

Check status of fuse(s)

Fuse(s) bad

Replace fuse(s) and see if blown fuse fault
recurs.
If problem recurs contact Customer Support.

Fuse(s) good

See below

Is the green LED lit

Yes

There is power to system but still does not
come on
Contact Customer Support.

No

There is no power to the LED
Contact Customer Support.

2

Screen is
blank

Screen is not
working

Verify if there is power
to system

No

Troubleshoot per item 1

Yes

See below

Is the ambient
temperature below or
above the operating
range of the screen (-
20ºC to +85)?

Yes

Screen is located in an area outside of the
temperature specifications.
Relocate transmitter.

No

See below

Are system signal
outputs (4-20 mA, etc)
in operation and
functional

Yes

– continue to use

system with DCS output

Possible damaged or faulty screen.
Contact Customer Support.

No

Contact Customer Support.