Flow meter faults (page 2) – CiDRA SONARtrac PW VF-100 User Manual

Page 268

Advertising
background image

20838-01 Rev 09

Page J-9

Flow Meter Faults (page 2)

Item
No

PROBLEM

POSSIBLE
CAUSE

DIAGNOSTIC
METHOD

DIAGNOSTIC
RESULT

COMMENTS

14

Flow does
not seem
correct

Sensor to transmitter
wiring may be faulty

Run ‘SENSOR CHECK’
in DIAGNOSTICS
menu

Yes

– passes all tests

See below

No

– fails one or more

tests

Verify and correct fault indicated on screen.
If problem persists, Acquire Snapshot, Upload
to secure Website, and contact Customer
Support.

One or more
sensors may be
faulty

Run ‘SENSOR
MAX/MIN’ in INFO
menu

Yes

– all sensors are

within 30% of each
other (process must be
flowing at nominal flow
rate)

See below

No

– one or more

sensors vary from the
others by >30%

Potential sensor failure.
Acquire Snapshot, Upload to secure Website,
and contact Customer Support.

Incorrect viscosity or
density settings

Verify correct settings in
BASIC CONFIG menu

Yes

– the proper

settings are input

See below

No - the settings are
not correct

Correct inputs in BASIC CONFIG menu

System is in
‘Initialize Mode’

Is the system
‘Heartbeat’ (indicated
by a spinning ‘\I/-‘ ) on
bottom right of screen
active

Yes

System is operational and communicating
with DSP.

No

The system is designed to reset automatically
after 30 minutes. If reset does not occur,
cycle power to system.
If this recurs, contact Customer Support.