CiDRA SONARtrac PW VF-100 User Manual

Page 140

Advertising
background image

20833-01 Rev 04

Page 7-46

Table 12 (page 6) VF/GVF Transmitter Menu Tree Software Release 04.02.XX

Level 1

Level 2

Level 3

Range

Description

Customize

Display

Line 1

Flow Rate, Totalizer,
Flow Rate %GVF, SOS,
True Liquid Flow, Blank

Parameter displayed on
line 1

Line 2

Flow Rate, Totalizer,
Flow Rate %GVF, SOS,
True Liquid Flow, Blank

Parameter displayed on
line 2

Contrast

0 to 1000 (default 170)

Contrast of display

Sensor Setup

State

On/off

Enable / disable each
sensor

Flow Units

Volume

gal, l, m

3

, user, ft

3

, igal,

ft, m

Flow units

Time

d, h, m, s, user

Time units

User Vol Label User defined

Custom flow vol label

Use Vol Base

gal, l, m

3

, ft

3

, igal, ft, m

Base units for custom
volume label

User Vol Scale

0.0000 e-38 to
9.9999 e+38

Scale factor on custom
volume base

User Time
Label

User defined

Custom time label

User Time
Base

d, h, m, s

Base units for custom
time label

User Time
Scale

0.0000 e-38 to
9.9999 e+38

Scale factor on custom
time base

SOS Units

Units

Feet or meters

Units of measure

Flow Cutoff
Range

Low End

0% to 100% (3 to 30
ft/s)

Under this value ‘<min
flow’ will be displayed

High End

0% to 100% (3 to 30
ft/s)

Over this value ‘>max
flow’ will be displayed

Totalizer

Units

gal, l, m

3

, ft

3

, user def

Units for totalizer

Lowcut Enable Enable, Disable

Turns totalizer lowcut
on / off

Lowcut

0% to 100% (3 to 30
ft/s)

Flow values below this
not used for totalizer

Multiplier

M, k, 1

Total Multiplier

Reset

Reset totalizer value

Input

Vol Flow

Totalized flow basis

Wr Protect
Mode

Enable, Disable

When enabled no other
parameters can be
changed