System Faults (page 4):

Item
No

PROBLEM

POSSIBLE
CAUSE

DIAGNOSTIC
METHOD

DIAGNOSTIC RESULT COMMENTS

8

The 4

–20mA

display in
control room
does not
match the
flow rate on
the meter

Wrong Range
settings at transmitter
or DCS

Verify the range settings
are the same

Yes - Ranges of transmitter
and DCS are the same

See below if problem persists

No

– range settings are

different

Re-range the DCS or the
transmitter

The transmitter
output trim needs to
be adjusted

Scroll to ‘4mA TRIM’ in the
4-20 mA CH 1(2) submenu
under the OUTPUT
CONFIG menu in order to
access trim function. Press
ENTER and follow
instructions

Yes

– the output is correct

See below

No

– the output needs to be

adjusted

Input values per transmitter screen
values. If problem persists see
below

Signal is being
affected by PLC card

Disconnect input signal
lines from PLC card.
Connect current meter to
leads. Output discrete mA
signals using ‘4-20mA
TEST’ under the
DIAGNOSTIC menu.

Yes

– the current meter

readings match the
transmitter output values

A 4-20mA signal isolator may be
required. Contact Customer
Support.

No

– the current readings do

not match the transmitter
values

See below

The 4-20mA values
generated by the
transmitter in ‘4-
20mA Test’ do not
match the signals
seen at the end of the
signal cable

Connect current meter at
the 4-20mA terminals in the
transmitter and output
discrete signals using ‘4-
20mA Test’

Yes - the signals output from
the transmitter match the
current meter readings

Plant wiring may have a problem.
Verify integrity of signal wires.

No

– the output from the

meter does not match the
current meter readings

Contact Customer Support.