20833-01 Rev 04

Page 7-8

Figure 5

Pulse Switch Closure

For sizing R

1

refer to the following example.

Power Supply = 24V

Choose a value for R

1

so as to not exceed 100mA

R

1

= 24V / 100mA = 240

Ω

Therefore, R

1

should be sized to be greater than

240Ω so the current does not exceed 100mA

Note: Recommended minimum swing pulse is 1 msec. At the 0.5
msec pulse width setting, the voltage across the solid-state relay will
be approximately 50% of power supply voltage.

7.3.3

ALARM

The alarm output consists of an electrically isolated switch closure
occurs between AL+ and AL- whenever the limits specified in the
transmitter setup for Alarm are met. These limits can be changed or
disabled through the local keypad and display. The maximum applied
voltage between AL+ and local ground and AL- and local ground shall
be within the range of +30V / -10V. The load current shall be a
maximum of 100mA.

The ‘EXIT’ key is used to clear alarms while in the Operational Mode.

Figure 6

Alarm Switch Closure

AL+ (HI)

AL- (LOW)

To
Counter
Inputs

R1

Out-

Out+

P-

P+

-

+

Power

Supply