7.3.5.2

Externally Powered 4-20mA Loop Configuration

The connections for a 4-

20mA interface configured as “Externally

Powered” are shown below. The maximum value of V

EXT

should be

chosen such that the maximum applied voltage between V

EXT

and

local ground and I

OUT

and local ground shall be within the range of

+30V / -10V and current limited to 100mA. The maximum value of R

L

is determined by the following equation:

R

L Max

= (V

EXT

– 8.35) / (0.022)

For example, with V

EXT

= 24VDC:

R

L Max

= (24-8.35) / (0.022) = 711 Ohms

In the externally powered configuration the 4-20mA interface is
capacitively isolated from the rest of the transmitter electronics
provided that the applied voltages are within +30V / -30V.

Figure 10

Externally Powered 4

–20mA Loop

7.3.6

SHD

The three SHD (shield) terminals should only be used for grounding
shields of any output wiring such as connections to CUR 1 or CUR2.
These should not be used for the SENSOR 1 or 2 shields or for the
Sensor Head to Transmitter cable shield. Only one end of the shield
wire should be connected to eliminate shield currents.

7.3.7

Fieldbus

Optional Foundation Fieldbus communications are available on
passive sonar meter transmitters. Refer to document USE OF
FOUNDATION FIELDBUS

®

PROTOCOL WITH PASSIVE SONAR

METER TRANSMITTERS.

Plant control system

R

L

+

-

V

EXT

Transmitter

4-20mA
driver