5–35

Programming

[Heatsink Temp]

This parameter displays the heatsink temperature.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

°

C

[Set Defaults]

Setting this parameter to “Defaults Init” resets all
parameters to their factory values.

This parameter cannot be changed while the drive is
running.

Parameter Number

64

Parameter Type

Read and Write

Factory Default

“Ready”

Units

Display Drive

“Ready” 0

Display after function complete.

“Store to EE” 1

Not implemented.

“Rcll frm EE” 2

Not implemented.

“Default Init” 3

Resets all parameters to factory
settings.

[Application Sts]

The value of this parameter provides a checksum
value that indicates a change in drive programming
has occurred.

With a Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on line 1.

Parameter Number

200

Parameter Type

Read Only

Factory Default

00000000

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Sync Input – 0 = Disabled, 1 = Enabled
P Jump – 0 = Disabled, 1 = Enabled

Unused

[DC Bus Memory]

This parameter displays the nominal DC bus voltage
level. This value is used to determine line loss,
overvoltage, decel frequency and other points.

Parameter Number

212

Parameter Type

Read Only

Display Units / Drive Units

1 Volt / Volts

Display

Volts

Diagnostics