15. Jog Control & Stop Mode Check.

A. With the drive reset, but not running,

press and hold the Jog key on the Con-
trol Panel. The motor should accelerate
to the frequency programmed by the
[Jog Frequency] parameter and remain
there until the Jog key is released.
When released, the drive should
execute a stop function using the pro-
grammed stop mode. Verify that the
correct stop mode was initiated.

Stopped

–0.00 Hz

At Speed

–10.00 Hz

Set to Maximum Frequency

16. Checking Accel and Decel Times.

A. Verify that the frequency command is

at maximum frequency.

B. Start the drive and observe the amount

of time the drive takes to accelerate to
maximum frequency. This should
equal 10 seconds, which is the factory
default value for the [Accel Time 1]
parameter.

C. Press the Reverse key and observe the

amount of time the drive takes to
decelerate from maximum frequency
to zero. This time should equal the
time set in the [Decel Time 1]
parameter (default is 10 seconds). If
these times are not correct for your
application, refer to Chapter 5 for
instructions on programming changes.

Important: With [Direction Mask] set to the
default value, the reverse command must
be issued from the HIM or other adapter. If
the reverse command is to be issued from
TB3, [Direction Mask] must first be
programmed to allow direction control
from TB3.

D. Stop the drive.

Stopped

+0.00 Hz

Remove ALL Power

17. Reconnect the Motor.

A. Remove and lock-out the input and

control power to the drive. When the
HIM Display is no longer illuminated,
remove the drive cover.