5–43

Programming

This group of parameters contains all the parameters necessary to activate encoder feed-
back for closed loop operation.

Encoder

Feedback

[Speed Control]

This parameter selects the type of speed modulation
active in the drive.

This parameter cannot be changed while the drive is
running.

Important: If encoder feedback closed loop speed
regulation is required, “Encoder Fdbk” must be
selected.

Parameter Number

77

Parameter Type

Read and Write

Factory Default

“No Control”

Units

Display Drive

“No Control” 0

Frequency regulation

“Slip Comp” 1

Slip compensation

“Speed Droop” 2

Negative slip compensation

“PLL” 3

Phase lock loop

“Encoder Fdbk” 4

Encoder feedback–closed loop

“Droop + Reg” 5

Enc. fdbk.–closed loop w/ active droop

“P Jump” 6

Traverse function

[Encoder Type]

This parameter contains the feedback encoder signal
type. The drive can accept single-ended, single-
channel (Pulse) or differential (Quadrature) signals.

This cannot be changed while drive is running.

Parameter Number

152

Parameter Type

Read and Write

Factory Default

“Pulse”

Units

Display Drive

“Pulse” 0

“Quadrature” 1

[Pulse/Enc Scale]

This parameter contains the scaling factor for both
pulse train inputs (TB2-7, 8) and encoder feedback
speed regulation (TB3 terminals 31-36).

1. Encoder Feedback Operation

Enter actual encoder pulses per revolution

2. Pulse Train Input

Scale

Factor

Incoming Pulse Rate (Hz)

Desired Command Freq.

Motor Poles

2

x

=

Parameter Number

46

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

64 PPR

Minimum Value

1

Maximum Value

4096

Pulse Train Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336–MOD–N1 option outputs 64 Hz/Hz.
At full analog reference, the pulse output will
be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.

Pulse/Enc Scale

3840 Hz

60 Hz

4 Poles

2

= 128

This value will create a command frequency of
60 Hz for full analog reference to the option.

=

x

[Maximum Speed]

This parameter sets the output frequency at full
frequency reference for:

1. Encoder feedback speed regulation.

2. All analog inputs to TB2 (remote pot, 0-10V &

0-20 mA).

NOTE: [Maximum Freq.] must be raised to allow
operation or modulation above [Maximum Speed].

Parameter Number

151

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 1

Factory Default

400 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[Motor Poles]

This parameter contains the number of motor
magnetic poles. This value translates output
frequency into actual motor RPM during closed loop
operation. It is calculated from
[Motor NP Hertz] and [Motor NP RPM].

Parameter Number

153

Parameter Type

Read Only

Display Units / Drive Units

1 Poles / Poles