4–2

Start-Up

Initial Operation – Motor Disconnected

1. Verify that AC line power at the disconnect device is within the

rated value of the drive. If a Control Interface option (L4, L5, L6,
L4E, L5E, L6E) is installed, verify that the control power to this
board matches the board rating.

2. Remove and lock-out all incoming power to the drive including

incoming AC power to terminals R, S and T (L1, L2 and L3) plus
any separate control power for remote interface devices. Remove
the drive cover and disconnect the motor leads from TB1,
terminals U, V, W (T1, T2 and T3).

3. If a Control Interface option is installed, verify that the Stop and

Enable interlock inputs are present. If an [Input Mode] other than
“1” is to be used, verify that the Auxiliary interlock input is
present.

Important:

The Stop and Enable inputs (and Auxiliary if
required) must be present before the drive will
start.

If this option is not installed, verify that two jumpers are installed
at pins 3 & 4 and 17 & 18 of J4 on A Frame drives or J7 on B
Frame and up drives. In addition, the [Input Mode] must be set to
“1.”

4. Confirm that all other optional inputs are connected to the correct

terminals and are secure.

5. The remainder of this procedure requires that a HIM be installed.

If the HIM has a Control Panel, use the local controls to complete
the start-up procedure. If a Control Panel is not present, remote
devices must be used to operate the drive.

6. Replace the drive cover and tighten the thumbscrew(s).