5–23

Programming

[FStart Reverse]

This value sets the frequency at which the reverse
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Reverse search ends at zero Hertz
or when motor speed is found.

Parameter Number

157

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

0 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

[Traverse Inc]

This value sets the traverse increase time
independently. See figure below.

Parameter Number

78

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Sec / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

30.00 Sec

[Traverse Dec]

This value sets the traverse decrease time
independently. See figure below.

Parameter Number

172

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Sec / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

30.00 Sec

[Max Traverse]

This value sets the peak amplitude of speed
modulation.

Parameter Number

79

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Hertz / 32767 = [Maximum Freq]

Factory Default

0.00 Hz

Minimum Value

0.00 Hz

Maximum Value

50% of [Maximum Freq]

Seconds

Hertz

Maximum Traverse (–)

Traverse

P-Jump

P-Jump (+)

P-Jump (–)

Output

Reference

Traverse Period

–20

0

10

20

30

40

50

60

20

40

Maximum Traverse (+)

Traverse Function

Feature Select