4–10

Start-Up

or

Set Power-Up Display

19. With HIM software versions 2.02 & up,

the power-up display (Status, Process or
Password) can be programmed to appear
when drive power is applied. Simply
access the desired display and
simultaneously press the Increment and
Decrement keys.

Set Electronic Overload

20. Electronic overload protection is factory

set to drive maximum.

A. To properly set the electronic overload

protection, program [Overload Amps]
(Setup group) to the actual nameplate
F.L.A.

B. If the motor speed range is greater than

2:1, program [Overload Mode] to the
proper derate.

21. This completes the basic start-up

procedure. Depending on your application,
further parameter programming may be
required. Refer to Chapter 5 for
information.

22. If password protection is enabled, log out

as described in Chapter 3.