Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 66
4–10
Start-Up
or
Set Power-Up Display
19. With HIM software versions 2.02 & up,
the power-up display (Status, Process or
Password) can be programmed to appear
when drive power is applied. Simply
access the desired display and
simultaneously press the Increment and
Decrement keys.
Set Electronic Overload
20. Electronic overload protection is factory
set to drive maximum.
A. To properly set the electronic overload
protection, program [Overload Amps]
(Setup group) to the actual nameplate
F.L.A.
B. If the motor speed range is greater than
2:1, program [Overload Mode] to the
proper derate.
21. This completes the basic start-up
procedure. Depending on your application,
further parameter programming may be
required. Refer to Chapter 5 for
information.
22. If password protection is enabled, log out
as described in Chapter 3.