4–3

Start-Up

Apply Power

7. Apply AC power and control voltages to

the drive. The LCD Display should light
and display a drive status of “Stopped” and
an output frequency of “+0.00 Hz.”

If the drive detects a fault, a brief state-
ment relating to the fault will be shown on
the display. Record this information,
remove all power and correct the fault
source before proceeding. Refer to Chapter
6 for fault descriptions.

Stopped

+0.00 Hz

Reset Factory Defaults

or

or

8. Important: The remaining steps in this

procedure are based on factory default
parameter settings. If the drive has been
previously operated, parameter settings
may have been changed and may not be
compatible with this start-up procedure or
application. Drive status and fault
conditions may be unpredictable when
power is first applied.

To obtain proper results, the parameters
must be restored to factory default settings.

A. From the Status Display, press Enter

(or any key). “Choose Mode” will be
displayed.

B. Press the Increment (or Decrement)

key until “EEPROM” is displayed. If
EEProm is not in the menu,
programming is password protected.
Refer to Chapter 3 for Password
information.

C. Press Enter.

D. Press the Increment (or Decrement)

key until “Reset Defaults” is
displayed.

E. Press Enter to restore all parameters to

their original factory settings.

F. Press ESC. “Reprogram Fault” will

display.

G. Press the Stop key to reset the fault.

Important: If [Input Mode] was previously
set to a value other than “1,” cycle drive
power to reset.

Choose Mode
Display

Choose Mode
EEProm

EEProm
Reset Defaults

Choose Mode
EEProm

Reprogram Fault
F 48

Stopped

+0.00 Hz