5–44

Programming

[Speed KI]

This parameter contains the integral gain value for
the velocity loop during closed loop operation.

Parameter Number

165

Parameter Type

Read and Write

Display Units / Drive Units

Numeric / Gain x 100

Factory Default

100

Minimum Value

0

Maximum Value

20000

[Speed Error]

This parameter displays the difference between
[Freq Command] and feedback speed.

Parameter Number

166

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq.

Factory Default

None

Minimum Value

– 8.33% of [Base Frequency]

Maximum Value

+ 8.33% of [Base Frequency]

[Speed Integral]

This parameter displays the integral value from the
speed loop.

Parameter Number

167

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq.

Factory Default

None

Minimum Value

–8.33% of [Base Frequency]

Maximum Value

+ 8.33% of [Base Frequency]

[Speed Adder]

This parameter displays the amount of correction
applied to the [Freq Command].

Parameter Number

168

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq.

Factory Default

None

Minimum Value

– 8.33% of [Base Frequency]

Maximum Value

+ 8.33% of [Base Frequency]

[Motor NP RPM]

This value should be set to the motor nameplate
rated RPM.

Parameter Number

177

Parameter Type

Read and Write

Display Units / Drive Units

1 RPM / RPM x 1

Factory Default

1750 RPM

Minimum Value

60 RPM

Maximum Value

24000 RPM

[Motor NP Hertz]

This value should be set to the motor nameplate
rated frequency.

Parameter Number

178

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 1

Factory Default

60 Hz

Minimum Value

1 Hz

Maximum Value

400 Hz

[Pulse/Enc Hertz]

This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

Encoder Feedback