Flt driv status, Fault alarms, Flt clear mode – Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 96: Ground warning, Faults

Advertising
background image

5–30

Programming

[Flt Driv Status]

This parameter stores and displays
the last [Drive Status] prior to a
fault.

Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.

With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.

Parameter Number

146

Parameter Type

Read Only

Enabled

Running

Command Direction

Actual Direction

Accelerating

Decelerating

Faulted

At Speed

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9

Bit 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Alarm

0 = Reverse

1 = Forward

0 = Reverse

1 = Forward

Reference

ID

Local

Adapter ID

Reference

15 14 13 12

Freq Select 1

0

0

0

0

Preset Freq 1

0

0

0

1

Preset Freq 2

0

0

1

0

Preset Freq 3

0

0

1

1

Preset Freq 4

0

1

0

0

Preset Freq 5

0

1

0

1

Preset Freq 6

0

1

1

0

Preset Freq 7

0

1

1

1

Freq Select 2

1

0

0

0

Adapter 1

1

0

0

1

Adapter 2

1

0

1

0

Adapter 3

1

0

1

1

Adapter 4

1

1

0

0

Adapter 5

1

1

0

1

Adapter 6

1

1

1

0

Jog Frequency 1

1

1

1

Local

11 10 9

TB3

0

0

0

1

0

0

1

2

0

1

0

3

0

1

1

4

1

0

0

5

1

0

1

6

1

1

0

Unused

1

1

1

Bit 14

[Fault Alarms]

This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.

With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.

Parameter Number

173

Parameter Type

Read Only

Bus Charging

Regenerating Current Limit

Regenerating Voltage Limit

Line Loss In Progress

Motor Stalled

Ground Warning

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9

Bit 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Overcurrent

Sync Loss

Bit 14

Hardware Current Limit

Motoring Current Limit

Unused

Unused

Voltage Check

Heatsink Temp

Auxiliary Input

4-20 mA Loss

[Flt Clear Mode]

This parameter controls the method for clearing
faults.

Parameter Number

39

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

Faults cleared only by cycling power

“Enabled” 1

Faults cleared by issuing a valid
stop command or cycling power

[Ground Warning]

Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.

Parameter Number

204

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Ground Warning Generated

Faults