Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 24

Advertising
background image

2–16

Installation/Wiring

Figure 2.3
TB2 Connections

1

Analog Out

Contacts Shown

in Unpowered State

10k Ohm

4-20mA

to

TE

0-10V

Pulse

Source

Reserved for

Future Use

CR2

TE

TE

CR1

Logic

Common

Only Present

on B Frame

& Up Drives

Only Present

on B Frame

& Up Drives

CR3

Typical

CR3

CR4

CR4

2

3

4

5

6

9

10

11

12

13

14

15

16

17

18

A1

A2

8

7

User Supplied
Analog Device

+

+

+

+

3.42k

100

100

52.3k

100

215

215

75k

47.5k

150

1.4k

1

µ

f

1

µ

f

1

µ

f

12 Bit

D/A

+5V

10 Bit

A/D

10 Bit

A/D

10 Bit

A/D

Table 2.E
Terminal Block TB2 Specifications

Terminal

Signal

TE

True Earth – Shield Termination

1, 2, 3

External Speed Pot. or Analog Trim Pot. (10k ohm pot. required)

2

4

Signal Common

5

0-10V DC Input

2

Input Impedance = 100k ohms

6

4-20mA Input

2

Input Impedance = 250 ohms

7, 8

Pulse Input

4

Refer to Pulse Input on the following page

9

Analog Output

1

Jumper JP1 to select 0-10V DC output

5

9

Analog Out ut
A Frame Drives

Jum er JP1 to select 0-10V DC out ut
Jumper JP2 to select 0-20mA output

6

Analog Output

1

B Frame Drives and Up

Jumper J5 selects output
pins 1-2 = 0-20mA

6

pins 3-4 = 0-10V DC

5

10, 11

CR1 Programmable Contact

11 12

CR2 Run Contact

11, 12

CR2 Run Contact

13, 14

CR3 Fault

Resistive Rating = 115V AC/30V DC, 5.0A

13, 14
14, 15

CR3 Fault
CR3 Fault NOT Contact

3

Resistive Rating 115V AC/30V DC, 5.0A
Inductive Rating = 115V AC/30V DC, 2.0A

16, 17

CR4 Alarm

g

5

C/30

C, 0

16, 17
17, 18

CR4 Alarm
CR4 Alarm NOT Contact

A1, A2

Reserved for Future Use