Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 88

Advertising
background image

5–22

Programming

[S Curve Time]

This creates an adjustable s curve ramp. If S Curve
Time is < the programmed accel/decel time, the
actual ramp will be the sum of the two. If S Curve
Time is

the programmed accel/decel times, a fixed

S curve will be created whose time is double the
programmed accel/decel time.

Parameter Number

56

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

0.0 Sec

Minimum Value

0.0 Sec

Maximum Value

3000.0 Sec

[Language]

This parameter selects between English and the
alternate language (not currently available) for the
HIM display.

Parameter Number

47

Parameter Type

Read and Write

Factory Default

“English”

Units

Display Drive

“English” 0

“Alternate” 1

[Speed Control]

This parameter selects the type of speed modulation
active in the drive.

This parameter cannot be changed while the drive is
running.

Important: If encoder feedback closed loop speed
regulation is required, “Encoder Fdbk” must be
selected.

Parameter Number

77

Parameter Type

Read and Write

Factory Default

“No Control”

Units

Display Drive

“No Control” 0

Frequency regulation

“Slip Comp” 1

Slip compensation

“Speed Droop” 2

Negative slip compensation

“PLL” 3

Phase lock loop

“Encoder Fdbk” 4

Encoder feedback–closed loop

“Droop + Reg” 5

Enc. fdbk.–closed loop w/ active droop

“P Jump” 6

Traverse function

[Flying Start En]

This value enables the flying start function and
chooses the method to be used. The drive will first
search from the direction it was last running.

Parameter Number

155

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Speed Search” 1

Freq. sweep –see [FStart For./Rev.]

“Use Encoder” 2

Requires feedback encoder

“Track Volts” 3

Read back EMF from sync. p.m.
motor

ATTENTION: The “Speed Search” selection should not be
used with synchronous or permanent magnet motors. Motors
may be demagnetized during braking.

!

[FStart Forward]

This value sets the frequency at which the forward
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Forward search ends at zero Hertz
or when motor speed is found.

Parameter Number

156

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz

Factory Default

60 Hz

Minimum Value

0 Hz

Maximum Value

400 Hz

Feature Select

Advertising