Installation/Wiring

Figure 2.6 c
Option L6/L6E Wiring

Typical

A

A

ENC
RET

ENC
12V

115V AC

Fuse

Common

Typical

12V

681

100

90.9

5V

JP4

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

0.15

µ

f

0.33

µ

f

0.22

µ

f

49

499k

20k

100

100

User Supplied

115V AC

Contacts shown are general, refer to Figure 2.5 for

Input Mode selection and recommended contact types.

Fuse

TB3

Option L6/L6E – 115V AC Interface Board Requirements

Circuits used with Option L6/L6E must be capable of operating with
high = true logic. In the low state, circuits must generate a voltage of
no more than 30V AC. Leakage current must be less than 10 mA into
a 6.5k ohm load. In the high state, circuits must generate a voltage of
90-115V AC

±

10% and source a current of approximately 20 mA for

each input. The L6/L6E option is compatible with these
Allen-Bradley PLC modules:

1771-OW

1771-OA

1771-OWN

1771-OAD

Encoder Wiring

Encoders must be line driver type, quadrature or pulse, 5V DC or
8-15V DC output, single-ended or differential and capable of
supplying a minimum of 10mA per channel. Maximum input
frequency is 125 kHz. Encoder inputs (TB3, terminals 31-36) cannot
be used if Pulse Train inputs (TB2-7, 8) are being used.