Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 86

Advertising
background image

5–20

Programming

This group contains the necessary parameters to activate and program advanced features
of the drive.

Feature Select

[Dwell Frequency]

This value sets the frequency that the drive will
immediately output (no Accel Ramp) upon a start
command. This parameter requires a programmed
[Dwell Time].

Parameter Number

43

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

0.0 Hz

Minimum Value

0.0 Hz

Maximum Value

7.0 Hz

[Dwell Time]

This value sets the time the drive will continue to
output [Dwell Frequency] before ramping to [Freq
Command].

Parameter Number

44

Parameter Type

Read and Write

Display Units / Units

1 Second / Seconds

Factory Default

0 Sec

Minimum Value

0 Sec

Maximum Value

10 Sec

Dwell Time

Frequency of

Applied Voltage

0

0

Time

Maximum

Dwell Frequency

Start
Command

Dwell

Time

[Slip @ F.L.A.]

Sets the amount of automatic increase or decrease
to the drive output to compensate for motor slip.
When [Speed Control] is set to “Slip Comp”, a
percentage of this value proportional to output
current is added to the drive output frequency. When
[Speed Control] is set to “Droop”, a percentage of
this value proportional to output current is subtracted
from the drive output frequency.

Parameter Number

42

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

0.0 Hz

Minimum Value

0.0 Hz

Maximum Value

5.0 Hz

[Run On Power Up]

This parameter enables the function that allows the
drive to automatically restart on Power Up. This
parameter requires that a two wire control scheme
be installed at TB3 and that a valid start contact be
present. Refer to Input Mode Selection figure in
Chapter 2.

Parameter Number

14

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

ATTENTION: This parameter may only be used as outlined in
NFPA79, paragraph 6-14 (exceptions 1-3) for specialized
applications. Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application.

!