Power Loss Ride-Thru

The 1336 plus has the ability to ride through short power
interruptions. On loss of input power to the drive, the drive offers
two methods of operation.

Diagram 1

With the Line Loss Fault parameter disabled, if a power
interruption occurs (T1) the drive will continue to operate off
stored DC bus energy until bus voltage drops to 85% of its
nominal value (T2). At this point, the drive output is shut off,
allowing the DC bus to discharge more slowly. The drive will
retain its logic and operating status as long as bus voltage is
above the absolute minimum bus voltage (refer to Appendix). If
bus voltage should fall below this level (T5), the drive will trip and
Undervolt Fault will be displayed. If input power is restored before
this minimum is reached (T3) and bus voltage rises above the
85% level (T4), the drive will restore output power to the motor
and resume running.

Diagram 2

With the Line Loss Fault parameter enabled, if input power is lost
(T1) the drive will continue to operate until the bus voltage falls
below 85% of nominal (T2). At this point the drive output is turned
off and a 500 ms timer is started. One of the following conditions
will then occur:

1. The bus voltage will fall below minimum before the time ex-

pires (T6). This will generate an Undervolt Fault.

2. The bus voltage will remain below 85% but above minimum

and the timer expires (T5). This will generate a Line Loss Fault.

3. The input power is restored (T3) and the bus voltage rises

above the 85% level before the timer expires (T4). This allows
the drive to turn its output on and resume running.

Output

DIAGRAM 1

T1

T1 = Loss of Power

T2 = Bus Level at 85% of Nominal, Outputs Shut Off

T3 = Power Returned

T4 = Outputs Turned On

T5 = Minimum Bus Voltage Level, Undervoltage Fault Point

T2

T4 T5

T3

Logic

Output

Off

100% V

BUS

85% V

BUS

Minimum V

BUS

Undervoltage Fault

(depends on [Low Bus Fault])

Output

T1

T1 = Loss of Power

T2 = Bus Level at 85% of Nominal, Outputs Shut Off

T3 = Power Returned

T4 = Outputs Turned On

T5 = 500mS Time Out, Line Loss Fault

T6 = Minimum Bus Voltage Level, Undervoltage Fault Point

T2

T4 T6

T5

T3

Logic

Output

Off

100% V

BUS

85% V

BUS

Minimum V

BUS

Undervoltage Fault

(depends on [Low Bus Fault])

Line Loss Fault

DIAGRAM 2