Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 75

Advertising
background image

5–9

Programming

[Decel Time 1]

This value determines the time it will take the drive
to ramp from [Maximum Freq] to 0 Hz. The rate
determined by this value and [Maximum Freq] is
linear unless [S Curve Enable] is “Enabled.” It
applies to any decrease in command frequency
unless [Decel Time 2] is selected.

Parameter Number

8

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

10.0 Sec

Minimum Value

0.0 Sec

Maximum Value

6000.0 Sec

[Base Frequency]

This value should be set to the motor nameplate
rated frequency.

Parameter Number

17

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

60.0 Hz

Minimum Value

25.0 Hz

Maximum Value

400.0 Hz

[Base Voltage]

This value should be set to the motor nameplate
rated voltage.

Parameter Number

18

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

Drive Rated Volts

Minimum Value

25% of Drive Rated Voltage

Maximum Value

120% of Drive Rated Voltage

[Maximum Voltage]

This parameter sets the highest voltage the drive will
output.

Parameter Number

20

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

Drive Rated Volts

Minimum Value

25% of Drive Rated Voltage

Maximum Value

120% of Drive Rated Voltage

[Minimum Freq]

This parameter sets the lowest frequency the drive
will output.

Parameter Number

16

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

0.0 Hz

Minimum Value

0.0 Hz

Maximum Value

120.0 Hz

[Maximum Freq]

This parameter sets the highest frequency the drive
will output.

This parameter cannot be changed while the drive is
running.

Parameter Number

19

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

60.0 Hz

Minimum Value

25.0 Hz

Maximum Value

400.0 Hz

Standard Volts-per-Hertz Pattern

Voltage

0

0

Frequency

Motor Rated

Base Voltage

Base Frequency

Maximum Voltage
Maximum Frequency

Motor Rated

Setup

Advertising