Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 103

Advertising
background image

5–37

Programming

This group of parameters contains binary masks for all control functions. The masks control
which adapters can issue control commands.

Masks

TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6

Each mask contains a bit for each adapter.
Individual bits can be set to “Zero” to lockout
control by an adapter or set to “1” to permit an
adapter to have control.

With a Series A (version 3.0) or Series B HIM,
a Status description (bit ENUM) is displayed
on line 1.

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Mask

Not Used

[Direction Mask]

This parameter controls which adapters can issue
forward/reverse commands.

Parameter Number

94

Parameter Type

Read and Write

Factory Default

01111110

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

[Start Mask]

This parameter controls which adapters can issue
start commands.

Parameter Number

95

Parameter Type

Read and Write

Factory Default

01111111

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

[Jog Mask]

This parameter controls which adapters can issue
jog commands.

Parameter Number

96

Parameter Type

Read and Write

Factory Default

01111111

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

[Reference Mask]

This parameter controls which adapters can select
an alternate reference; [Frequency Sel 1],
[Frequency Sel 2] or preset speeds.

Parameter Number

97

Parameter Type

Read and Write

Factory Default

01111111

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

[Accel Mask]

This parameter controls which adapters can select
[Accel Time 1] and [Accel Time 2].

Parameter Number

98

Parameter Type

Read and Write

Factory Default

01111111

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

[Decel Mask]

This parameter controls which adapters can select
[Decel Time 1] and [Decel Time 2]

Parameter Number

99

Parameter Type

Read and Write

Factory Default

01111111

Units

Display Drive

“0” 0

Deny Control

“1” 1

Permit Control

Advertising