Programming

[DC Hold Time]

This value sets the amount of time that the
[DC Hold Level] voltage will be applied to the motor
when the stop mode is set to either
”DC Brake” or “Ramp.”

Important: Assure that [DC Hold Level] is set for a
value that is adequate for motor protection when
maximum DC hold is selected.

Parameter Number

12

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

0.0 Sec

Minimum Value

0.0 Sec

Maximum Value

1000 Sec

[DC Hold Level]

This value sets the DC voltage applied to the motor
to produce the selected current during braking,
when the stop mode is set to either “DC Brake” or
“Ramp.”

Parameter Number

13

Parameter Type

Read and Write

Display Units / Drive Units

1 % of [Rated Amps] / 4096 = 100%

Factory Default

100 %

Minimum Value

0 %

Maximum Value

150 %

ATTENTION: If a hazard of injury due to movement of
equipment or material exists, an auxiliary mechanical braking
device must be used to stop the motor.

ATTENTION: This feature should not be used with
synchronous or permanent magnet motors. Motors may be
demagnetized during braking.

!

Volts/Speed

Ramp-to-Stop

Time

Stop Command

e

g

a

tl

o

V

d

e

e

p

S

DC Hold Level

DC Hold

Time

Brake-to-Stop

Volts/Speed

Voltage

Time

Stop Command

Speed

DC Hold Level

DC Hold

Time

[Bus Limit En]

Enables the function that attempts to limit the drive
DC bus voltage to 110% of nominal voltage during
rapid decel. If bus voltage rises above the 110% level,
[BUS Limit En] reduces or stops the drive decel rate
until bus voltage falls below the 110% level.

Parameter Number

11

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

Allow bus voltage to rise above
110%.

“Enabled” 1

Limit bus voltage/decel ramp.

[Motor Type]

This parameter should be set to match the type of
motor connected to the drive.

Parameter Number

41

Parameter Type

Read and Write

Factory Default

“Induction”

Units

Display Drive

“Induction” 0

Requires no additional setting.

“Sync Reluc” 1

[Slip @ F.L.A.] must be set to zero.

“Sync PM” 2

[Stop Select 1 & 2] must be set to a
selection other than “DC Brake” and
[Slip @ F.L.A.] be set to zero.