Mechanical configuration – Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 144
C–4
CE Conformity
Frames A2 - A4
2
Frame B
2
To Motor
1
Cable Supplied with Filter
1
Conduit
1
To Motor
1
Three-Phase Input
1
Access
Panel
Flat Washer
Star Washers
Bolt
Bolt
Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and
in close proximity to one another.
Important: A positive electrical bond must
be maintained between drive and filter at
all 4 corners. Star washers can be
eliminated if a positive electrical
bond is assured.
Three-Phase
Input
1
1
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation.
Shielding/armor must be bonded to the metal bottom plate. See requirements 6 & 7 on page C–1.
2
Refer to the Filter Selection table on page C–2 for frame references and corresponding catalog numbers.
Required Knockout Assignments
Dimensions are in Millimeters and (Inches)
Frames B1/B2
Frames A2 through A4
Control I/O
Control I/O
Filter Input
Filter Input
SCANport
Motor Output
Motor Output
SCANport
28.6/34.9 (1.13/1.38) - 3 Plcs.
22.2 (0.88) - 1 Plc.
22.2 (0.88) - 1 Plc.
22.2/28.6 (0.88/1.13) - 3 Plcs.
Mechanical Configuration