Mechanical configuration – Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 144

Advertising
background image

C–4

CE Conformity

Frames A2 - A4

2

Frame B

2

To Motor

1

Cable Supplied with Filter

1

Conduit

1

To Motor

1

Three-Phase Input

1

Access

Panel

Flat Washer

Star Washers

Bolt

Bolt

Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and
in close proximity to one another.

Important: A positive electrical bond must
be maintained between drive and filter at
all 4 corners. Star washers can be
eliminated if a positive electrical
bond is assured.

Three-Phase

Input

1

1

Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation.
Shielding/armor must be bonded to the metal bottom plate. See requirements 6 & 7 on page C–1.

2

Refer to the Filter Selection table on page C–2 for frame references and corresponding catalog numbers.

Required Knockout Assignments

Dimensions are in Millimeters and (Inches)

Frames B1/B2

Frames A2 through A4

Control I/O

Control I/O

Filter Input

Filter Input

SCANport

Motor Output

Motor Output

SCANport

28.6/34.9 (1.13/1.38) - 3 Plcs.

22.2 (0.88) - 1 Plc.

22.2 (0.88) - 1 Plc.

22.2/28.6 (0.88/1.13) - 3 Plcs.

Mechanical Configuration